82 Parameters
No.
Name/Value/Range
Description
Default
FbEq (16b/32b)
178 MPPT settings
178.03
Minimum voltage ref
Sets the minimum MPPT voltage reference.
500 V
0 … 1000 V
1 = 1 V
178.04
Maximum voltage ref
Sets the maximum MPPT voltage reference.
950 V
0 … 1000 V
1 = 1 V
178.12
Zero power level
Sets power level in percent of nominal output
power where MPPT considers power to equal 0%
and starts to reduce the DC voltage. This avoids
MPPT from drifting at voltages above the panel
open circuit voltage.
1%
0 … 10%
1 = 1%
178.50
MPPT status word
Shows the MPPT status word.
b0: MPPT
MPPT is active.
b1: Limited mode
Tracking is not active because active power is
limited.
b2: Minimum voltage
MPPT reference is at the minimum voltage.
b3: Maximum voltage
MPPT reference is at the maximum voltage.
b4...b15: Reserved
178.51
Input power
Shows sum of DC string input power.
-
-
100 = 1 kW