Chapter 3 - Handling of Control Panel CDP 31x
IV A
3 - 8
DCS 500B / DCP 500B Operating Instructions
3.6 FAULT RESETTING (RESET)
FAULT resetting and EMERGENCY STOP resetting (RESET) can
only be performed via the CDP 31x if LOCAL is active. If drive is in
REMOTE, please check whether LOCAL is a critical condition. If not
activate LOCAL, reset the fault and activate REMOTE again.
Step
Function
Press key
Display after key is
pressed
1.
To enter the Actual Signal
Display Mode
ACT
0 L 0.0 rpm 00
DCS500
*** FAULT ***
I/O-Board not found
2.
To RESET the FAULT
RESET
0 L 0.0 rpm 00
SPC:OUT 0.0 %
CONV CUR 0 A
U ARM AC 0 V
_
3.7 EMERGENCY STOP RESETTING (RESET)
Step
Function
Press key
Display after key is
pressed
1.
If EMERGENCY STOP is acti-
vated, the control panel will
show the following ALARM
0 L 0.0 rpm 00
DCS500
** WARNING **
+Emergency stop
2.
To enter the Fault History Dis-
play
0 L 0.0 rpm 00
1 LAST FAULT
+Emergency stop
xxxx:xx:xx.xx
3.
To RESET the ALARM
RESET
0 L 0.0 rpm 00
1 LAST FAULT
-Emergency stop
xxxx:xx:xx.xx