Functions
Chapter 10
134
1SFC132003M0201
10:4 Tune torque control
Path in menu:
Menu/SETTINGS/Functional Settings/Torque control/
Tune T-Ctrl
With this parameter it is possible to change the speed of the
regulator that regulates the voltage so that the torque will
follow a predefined torque curve. In most cases, this
parameter will not have to be changed from its default value
which is 100%. If a dip occurs in the torque curve during stop,
increasing this parameter can solve the problem. This
parameter should not be set too high though, since this can
cause the torque of the motor to oscillate around the
predefined torque curve. If this is the case, decrease this
parameter.
10:5 Start ramp
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Start Ramp
When a start signal is given the softstarter performs a start
ramp by controlling the output voltage to the motor so that
either the voltage or the torque increases from the start level
to full voltage, depending on which ramp type is selected.
The start ramp continues until full voltage is applied to the
motor.
Parameter
text
Default value Setting range
Description
Tune T-Ctrl 100%
30...300%
The speed of the
regulator
1SFC132095F0001
Figure 5: Start ramp
Start
Parameter
text
Default value Setting range
Description
Start Ramp 10 s
1...30s, 1...120s
(Range depends
on Start Range)
Time for start
ramp
Summary of Contents for PST30
Page 2: ...This manual belongs to...
Page 4: ......
Page 8: ...Chapter 8 1SFC132003M0201 Notes...
Page 10: ...Introduction 10 1SFC132003M0201...
Page 14: ...Introduction Chapter 1 14 1SFC132003M0201...
Page 16: ...Quickstart 16 1SFC132003M0201...
Page 20: ...Description 20 1SFC132003M0201...
Page 34: ...Description Chapter 3 34 1SFC132003M0201...
Page 36: ...Mounting 36 1SFC132003M0201...
Page 40: ...Mounting Chapter 4 40 1SFC132003M0201...
Page 42: ...Connection 42 1SFC132003M0201...
Page 60: ...Connection Chapter 5 60 1SFC132003M0201...
Page 62: ...Human Machine Interface HMI 62 1SFC132003M0201...
Page 74: ...Human Machine Interface HMI Chapter 6 74 1SFC132003M0201...
Page 76: ...Setting and configuration 76 1SFC132003M0201...
Page 120: ...Fieldbus communication option 120 1SFC132003M0201...
Page 124: ...Maintenance 124 1SFC132003M0201...
Page 126: ...Maintenance Chapter 9 126 1SFC132003M0201...
Page 130: ...Chapter 130 1SFC132003M0201...
Page 178: ...Trouble shooting 178 1SFC132003M0201...
Page 188: ...Trouble shooting Chapter 11 188 1SFC132003M0201...
Page 190: ...Diagrams 190 1SFC132003M0201...
Page 199: ......