Chapter 10
Functions
10:55 Start ramp, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./Start Ramp1
This parameter makes it possible to set the start ramp time for the first parameter set.
Parameter text Default value Setting range
Description
Start Ramp1
10 s
1...30s, 1...120s First sequence, time for start ramp
10:56 Initial voltage, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./Init Volt1
This parameter makes it possible to set the initial voltage for the first parameter set.
Parameter text Default value Setting range
Description
Init Volt1
30%
30...70%
First sequence, initial voltage for start ramp
10:57 Current limit, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./Curr Lim1
This parameter makes it possible to set the current limit level for the first parameter set.
Parameter text Default value Setting range
Description
Curr Lim1
4 x Ie
2.0...7.0xle
First sequence, current limit
10:58 Setting current, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./1st Set Ie
This parameter makes it possible to set the rated motor current for the first parameter set.
Parameter text Default value Setting range
Description
1st Set Ie
Ir
9...1207A divided into 19 over-
lapping ranges
First sequence, current limit
10:59 Start ramp, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Start Ramp2
This parameter makes it possible to set the start ramp time for the second parameter set.
Parameter text Default value Setting range
Description
Start Ramp2
10s
1...30s, 1...120s Second sequence, time for start ramp
10:60 Initial voltage, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Init Volt2
This parameter makes it possible to set the initial voltage for the second parameter set.
Parameter text Default value Setting range
Description
Init Volt2
30%
30...70%
Second sequence, initial voltage for start ramp