Description
| Installation and commissioning manual | 1SFC132081M0201
3.1.1 Operation
functions
Available functions are listed below:
• Voltage start ramp
• Voltage stop ramp
• Torque start ramp
• Torque stop ramp
• Full voltage start
• No
ramp
• Stand-still
brake
• Current
limit
• Kick
start
• Slow
speed
• Motor
heating
• Sequence
start
• Automatic
restart
3.1.2 Protection
functions
The PSTX Softstarter has protection functions to
protect the Softstarter, motor and other equipment. All
protections can have automatic reset or manual reset.
You can enable or disable the protection.
Available protections are listed below:
• EOL
protection
• Locked rotor protection
• Phase reversal protection
• Current imbalance protection
• Overvoltage
protection
• Under voltage protection
• Ground fault protection
• Voltage imbalance protection
• Voltage outputs protection
• External thermal sensor - PT100 protection
• External thermal sensor - PTC protection
• Power factor underload protection
• Current underload protection
• User defined protection
• Too long current limit protection
• Bypass open protection
• Fieldbus failure protection
• Extension IO failure protection
• HMI failure protection
• Max number of starts
This chapter gives a description of the Softstarter in
general, specifications and available components and
spare parts.
3.1 Overview
The PSTX Softstarter has the latest technology for
soft start and soft stop of squirrel cage motors. The
Softstarter has multiple advanced motor protection
features as standard.
WARNING
If using the Rated Operational Voltage U
e
(Phase
/N) as source for Control Supply Voltage U
s
make
sure to not exceed U
s
250V AC,50/60Hz.
Bypass
Softstarter range PSTX30...1250 have integrated bypass
components.
User interface
The keypad on the front has Navigation keys, Selection
soft keys, Start and Stop keys, Local or Remote key,
Information key and a clear information screen. You can
select 15 user languages.
You can control the Softstarter in 3 different ways:
• Hardwire inputs control
• Keypad control (either attached to the Softstarter front
or detached and connected with the cable included)
• Fieldbus communication interface (by built in Modbus,
Anybus module or the FieldBus Plug with adapter)
You can use only one type of control at the same time.
Default selection is hardwire inputs control.
INFORMATION
Keypad control has the highest priority and
overrides all other control methods.
Fans
The integrated fans for cooling will run for 3 min
after each ramp (start/stop) and when the heatsink
temperature is too hot.
For PSTX1050…1250 the fans will run continuously in
TOR. A thermistor monitors the temperature.
3
Summary of Contents for PSTX Series
Page 1: ...1SFC132081M0201 Softstarters Type PSTX30 PSTX1250 Installation and commissioning manual...
Page 4: ......
Page 6: ......
Page 10: ...10 Introduction Installation and commissioning manual 1SFC132081M0201 1...
Page 16: ...16 Quick start Installation and commissioning manual 1SFC132081M0201 2...
Page 29: ...1SFC132081M0201 Installation and commissioning manual Description 29 3...
Page 30: ...30 Description Installation and commissioning manual 1SFC132081M0201 3...
Page 36: ...36 Installation Installation and commissioning manual 1SFC132081M0201 4...
Page 50: ...50 Connection Installation and commissioning manual 1SFC132081M0201 6...
Page 72: ...72 Human machine interface HMI Installation and commissioning manual 1SFC132081M0201 6...
Page 143: ...1SFC132081M0201 Installation and commissioning manual Functions 143 7...
Page 144: ...144 Functions Installation and commissioning manual 1SFC132081M0201 7...
Page 148: ...148 Communication Installation and commissioning manual 1SFC132081M0201 8...
Page 156: ...156 Maintenance Installation and commissioning manual 1SFC132081M0201 9...
Page 168: ...168 Troubleshooting Installation and commissioning manual 1SFC132081M0201 10...
Page 176: ...176 Wiring and application diagrams Installation and commissioning manual 1SFC132081M0201 11...
Page 181: ...1SFC132081M0201 Installation and commissioning manual Third party licenses 181 12...
Page 183: ...1SFC132081M0201 Installation and commissioning manual Revision 183 13...
Page 187: ...1SFC132081M0201 Installation and commissioning manual Index 187 14...