1SFC132081M0201 | Installation and commissioning manual |
Functions
89
7.12 Sequence
start
The Softstarter can start up to 3 different motors
sequentially, sequence 1, 2 and 3. This is suitable when
setting up the Softstarter with different applications.
Select the parameter set through input signal to the
Softstarter.
Parameter settings and physical connections for
programmable inputs must agree.
WARNING
EOL does not work during Sequence start.
Recommended to add separate overload
protections for each motor.
For connections, see
chapter
5.1.2.5 Programmable
inputs (Sequence start)
)
.
Parameters set for sequence start 1, 2 and 3 are equal.
If the Softstarter trips, and the trip must stop the motor,
all motors stop.
Sequence start has these parameters:
Parameter
Description
Setting range
Default value
08.01 Sequence mode
Enable sequence start of motors.
Off, Start multiple
motors
Off
08.02 Ie seq 1
08.30 seq 2
08.60 seq 3
Sets the nominal current for the motor.
For good performance, it is important that
the nominal current is set to the correct
value. For Inside Delta connection, set this
parameter to 58% of the nominal motor
current.
Individual
(different for each
type)
9.0 A...1250 A,
divided into 19
overlapping ranges
08.03 Start mode seq 1
08.31 seq 2
08.61 seq 3
Sets the desired start mode.
Voltage start ramp,
Torque start ramp,
Full voltage ramp
Voltage start ramp
08.04 Start ramp time seq 1
08.32 seq 2
08.62 seq 3
Sets the time it takes for the voltage to come
at 100%.
1 ... 120 s
10 s
08.05 Start ramp init lev seq 1
08.33 seq 2
08.63 seq 3
Sets the level from where the start ramp
initiates (voltage level for Voltage start and
torque level for Torque start).
10 ... 99%
30%
08.06 Curr lim lev seq 1
08.34 seq 2
08.64 seq 3
Sets the level to which the current is limited
during start.
0.5 ... 7.5 × Ie
7.0 × Ie
08.07 Kick start seq 1
08.35 seq 2
08.65 seq 3
Enables a voltage peak at the beginning of
the start ramp.
Information: The function Current Limit is not
in operation during Kick start.
Off, On
Off
08.08 kick start level seq 1
08.36 seq 2
08.66 seq 3
Sets the level of the Kick start in percentage
of rated voltage.
50 ... 100%
70%
08.09 Kick start lvl seq 1
08.37 seq 2
08.67 seq 3
Sets the duration of the Kick start in
seconds.
0.2 ... 2.0 s
0.2 s
08.06 Torque lim lvl seq 1
08.38 seq 2
08.68 seq 3
Sets the level to which the torque is limited
during the start with torque control.
20 ... 200%
150%
08.10 Torque tune seq 1
08.39 seq 2
08.69 seq 3
Adjustment of resistive losses.
0 ... 1000%
100%
08.11 Torque ctrl gain seq 1
08.40 seq 2
08.70 seq 3
Sets the speed of the voltage regulator
during torque start and stop. It seldom
needs to be changed, but if a dip occur in
the torque curve during stop, increasing this
value might solve it.
0.01 ... 10.0
0.24
Example: Start 1, (Start mode seq 1) is set to Run 1
relay , (K4,K5 or K6) the relay closes when the start
signal is given, which leads to a power transfer. This
can change between Softstarters and their specific
parameter settings.
7
Summary of Contents for PSTX Series
Page 1: ...1SFC132081M0201 Softstarters Type PSTX30 PSTX1250 Installation and commissioning manual...
Page 4: ......
Page 6: ......
Page 10: ...10 Introduction Installation and commissioning manual 1SFC132081M0201 1...
Page 16: ...16 Quick start Installation and commissioning manual 1SFC132081M0201 2...
Page 29: ...1SFC132081M0201 Installation and commissioning manual Description 29 3...
Page 30: ...30 Description Installation and commissioning manual 1SFC132081M0201 3...
Page 36: ...36 Installation Installation and commissioning manual 1SFC132081M0201 4...
Page 50: ...50 Connection Installation and commissioning manual 1SFC132081M0201 6...
Page 72: ...72 Human machine interface HMI Installation and commissioning manual 1SFC132081M0201 6...
Page 143: ...1SFC132081M0201 Installation and commissioning manual Functions 143 7...
Page 144: ...144 Functions Installation and commissioning manual 1SFC132081M0201 7...
Page 148: ...148 Communication Installation and commissioning manual 1SFC132081M0201 8...
Page 156: ...156 Maintenance Installation and commissioning manual 1SFC132081M0201 9...
Page 168: ...168 Troubleshooting Installation and commissioning manual 1SFC132081M0201 10...
Page 176: ...176 Wiring and application diagrams Installation and commissioning manual 1SFC132081M0201 11...
Page 181: ...1SFC132081M0201 Installation and commissioning manual Third party licenses 181 12...
Page 183: ...1SFC132081M0201 Installation and commissioning manual Revision 183 13...
Page 187: ...1SFC132081M0201 Installation and commissioning manual Index 187 14...