7.17.2 External faults
7.17.2.1
Phase loss fault
Voltage to one or more phases missing. For example, this
detects an open line contactor.
Check that the mains are connected. Check that no line
contactor or breaker is open.
Phase loss fault is configured with the following
parameters:
Parameter
Description
Setting range
Default value
26.01
Phase loss out
Specifies the Event groups this
fault belongs to.
Eventgroup 0 ... 6
1
26.02
Phase loss op
Set the operation of this fault.
Stop manual, Stop
auto
Stop manual
7.17.2.2
Bad network fault
Bad network quality fault is signaled if there is too much
frequency disturbance in the network. Then it will be too
dificult to control the triggering of the thyristors in a safe
way.
Check for harmonics or frequency disturbance in the
supply network.
Bad network fault is configured with the following
parameters:
Parameter
Description
Setting range
Default value
26.03
Bad network out
Specifies the Event groups this
fault belongs to.
Eventgroup 0 ... 6
1
26.04
Bad network op
Set the operation of this fault.
Stop manual, Stop
auto
Stop manual
7.17.2.3
Low supply voltage fault
Too low control supply voltage on terminals 1 and 2.
A fault signal will be given if the softstarter detects that
the control supply voltage is too low. Then it will stop the
motor and save unsaved data. However, if the control
supply voltage goes up before the softstarter is completely
turned off, the low supply voltage fault will be activated.
If the voltage is too low, it can no longer assure proper
function of the softstarter and this fault is signaled. This
fault can only be asserted after some time, since low
voltage will also be detected when the softstarter is
unplugged and shutdown.
Check for voltage dips or interruptions.
Low supply fault is configured with the following
parameters:
Parameter
Description
Setting range
Default value
26.05
Low supply voltage out
Specifies the Event groups this
fault belongs to.
Eventgroup 0 ... 6
1
26.06
Low supply voltage op
Sets the operation of this fault.
Stop manual, Stop
auto
Stop manual
7
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Summary of Contents for PSTX105
Page 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 6: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 10: ...1 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 16: ...2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 26: ...3 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 32: ...4 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 44: ...5 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 64: ...6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 124: ...7 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 128: ...8 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 131: ...9 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 132: ...9 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 142: ...10 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 145: ...11 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...