7.15.1 EOL Protection
The motor has been overloaded because of too high
current over a certain time. Check starting conditions and
EOL settings.
EOL protection is configured with the following
parameters:
Parameter
Description
Setting range
Default value
13.01
EOL mode
Set the EOL mode to Normal or Dual.
Normal/ Dual
Normal
13.02
EOL class
Sets the EOL trip class.
10 A, 10,
20, 30
10
13.03
EOL dual class
Sets the protection class used when in top
of ramp. This parameter is only applicable
when EOL protection mode is set to dual.
10 A, 10,
20, 30
10 A
13.04
EOL out
Specifies the Event groups this protection
belongs to.
Eventgroup 0 ...6
2
13.05
EOL operation
Sets the operation of this protection.
Off, Stop-Manual,
Stop-Automatic,
Indication
Stop-Manual
7.15.2 Locked rotor protection
The motor is running stiff. A damaged bearing or a
stucked load could be possible causes.
This protection is only operational in the top of ramp state.
Check the load and the motor.
Locked rotor protection is configured with the
following parameters:
Parameter
Description
Setting range
Default value
13.06
Locked rotor level
Set the locked rotor trip level
0.5 ... 8.0 x Ie
4.0 x Ie
13.07
Locked rotor trip time
Sets the time that the current has to be
above the trip level to trip.
1.0 ... 30.0 s
1.0 s
13.08
Locked rotor delay time
Sets the time after top of ramp that the
protection is enabled.
0.2 ... 10.0 s
5.0 s
13.09
Locked rotor out
Specifies the Event groups this protection
belongs to.
Eventgroup 0 ... 6
2
13.10
Locked rotor op
Sets the operation of this protection.
Off, Stop-Manual,
Stop-Automatic,
Indication
Off
7.15.3 Max number of starts protection
TBD
Max number of starts protection is configured with the
following parameters:
Parameter
Description
Setting range
Default value
13.11
Max no of starts per hour
Sets the limitation in number of starts per
hour.
1 ... 100
6
13.12
Max no of starts per hour out
Specifies the Event groups this protection
belongs to.
Eventgroup 0 ... 6
2
13.13
Max no of starts per hour op
Sets the operation of this protection.
Off, Stop-Manual,
Stop-Automatic,
Indication
Off
7
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Summary of Contents for PSTX105
Page 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 6: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 10: ...1 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 16: ...2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 26: ...3 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 32: ...4 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 44: ...5 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 64: ...6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 124: ...7 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 128: ...8 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 131: ...9 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 132: ...9 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 142: ...10 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 145: ...11 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...