background image

4.2.6.1   

Mounting Detachable HMI

A cable is included in the shipment, but it is also 
possible to use your own RJ45 network cable. 
The cable length should be max 3m long to 
minimize distortion of the communication.

The softstarter HMI is IP66 approved when 
mounted on the enclosure door.

The detachable HMI can also be used to copy parameters 
from one softstarter to another during commissioning 
(temporarily handheld).  

Included with the softstarter comes:

Rubber gasket

Plastic screw-nut

RJ45 Network cable

1.

Remove the detachable HMI from the softstarter by
unsnapping the plastic latch under the detachable
HMI, see 

1

 and 

2

 in 

Figure 20.

2.

Drill a hole were the detachable HMI is to be
mounted. Maximum size of the hole is Ø26
(Ø 1.02”), see 

1

 in 

Figure 21.

 Put the rubber

packing around the threaded network connector on
the detachable HMI, see 

2

 in 

Figure 21. 

Press the

the threaded network connector through the drilled
hole.
See 

3

 in 

Figure 21. 

Fasten the plastic screw-nut

on the threaded network connector, with 2 Nm
(17.7 lb/in).

3.

Remove the RJ45 plug see 

4

. Connect one end of

the network cable to the network port on the front
of the softstarter 

5

 in 

Figure 21.

4.

Connect the other end of the network cable to the
network port on the back of the detachable HMI,
see 

6

 in 

Figure 22.

5.

Make sure that the network cable is properly
inserted into both ports. Roll the rest of the
hanging cable so it will not get clamped by the
door, see 

7

 in 

Figure 23.

 Close the door of the

enclosure and switch on the operational voltage to
control that the external HMI is working.

2 Nm  (17,7 lb.in)

(Ø 1.02”)

Ø26

Min. Ø25,5 (Ø 1,0”)

Max. Ø28 (Ø 1,1”)

20

1SFC132081M0201

Figure 20: 

Drill a hole for the detachable keypad. 

1

2

3

21

1SFC132081M0201

Figure 21: 

Connect one end of the network cable.

5

4

22

1SFC132081M0201

Figure 22: 

Connect the other end of the network cable.

6

23

1SFC132081M0201

Figure 5: 

Roll the rest of the hanging cable.

7

4

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Summary of Contents for PSTX30

Page 1: ...Softstarters Type PSTX30 PSTX370 Installation and commissioning manual 1SFC132081M0201 EN Rev A Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 2: ...she is kindly asked to notify us as soon as pos sible The data contained in this manual is intended solely for the product description and is not to be deemed to be a state ment of guaranteed propert...

Page 3: ...he transportation company or the ABB reseller office immediately Do not lift the softstarter by the connection bars as this can do damage to the softstarter Saftey notes In this user manual these symb...

Page 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 5: ...ting 5 Connection 6 Human machine interface HMI 7 Functions 8 Communication 9 Maintenance 10 Troubleshooting 11 Wiring diagrams 12 Revisions Softstarters Type PSTX Installation and commissioning manua...

Page 6: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 7: ...nstallation and commissioning manual 1 2 Intended audience 9 1 3 Revision notes and other documents 9 1 4 Acronyms and abbreviations 9 1 4 Acronyms and abbreviations 9 1 Introduction Phone 800 894 041...

Page 8: ...3 Index Index of the content of this manual 1 1 2 Installation and commissioning manual Short form The Softstarters Type PSTX30 PSTX370 Installation and comissioning manual Short form contains brief i...

Page 9: ...ns The acronyms and abbreviations described in table 3 are used in this manual Table 3 Acronyms and abbreviations Acronym abbreviation Description BP By pass DOL Direct on line EOL Electronic overload...

Page 10: ...1 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 11: ...nnection 12 2 2 Configuration 14 2 2 1 Basic set up 14 2 2 2 Application set up 14 2 3 How to start stop the motor 15 2 Quick start Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info cl...

Page 12: ...o operational voltage INFORMATION ABB personell have to obey the instructions in ABB CISE 15 4 2 1 Connection 1 Mount the softstarter according to chapter 4 Mounting INFORMATION PSTX softstarters can...

Page 13: ...AC 15 and 30 V DC 5 A DC 12 See Figure 6 8 Check that the operational voltage and control supply voltage corresponds to the softstarter ratings 9 Switch on the control supply voltage 10 The green Read...

Page 14: ...on keys to select Yes or No and then press Save 7 Press and then Press Done to finish the Basic setup For more settings enter Application set up 2 2 2 Application set up 1 Find the Assistants menu fro...

Page 15: ...open the by pass relays see step 6 in chapter 2 1 Connection Opening the by pass relays is necessary to avoid unintentional starting of the equipment while it is being connected to operational voltag...

Page 16: ...2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 17: ...ctions 19 3 1 5 Softstarter overview 20 3 1 6 Type designation 21 3 1 7 Environmental influence 21 3 1 8 Specifications 21 3 2 Technical data 22 3 2 1 General 22 3 2 2 Technical data for external keyp...

Page 18: ...e softstarter has several advanced motor protection features as standard Bypass Softstarter range PSTX30 370 have integrated by pass components For PSTX210 370 this is a three phase by pass contactor...

Page 19: ...nt imbalance warning Over voltage warning Under voltage warning EOL time to trip warning EOL warning Total Harmonic Distortion THD warning Voltage imbalance warning Power factor underload warning Curr...

Page 20: ...this interface Overview See Figure 8 Ready Run Fault Protection Com1 Com2 4T2 2T1 6T3 3L2 1L1 5L3 PSTX L 100 250V 50 60 Hz K4 K5 K6 Start Stop In1 In2 DGND 24V GND N In0 8 1SFC132081M0201 Figure 8 So...

Page 21: ...ications General data Description Degree of protection Main circuit PSTX30 105 IP10 PSTX142 370 IP00 Degree of protection Supply and control circuit PSTX30 105 IP20 PSTX142 370 IP20 Operating position...

Page 22: ...play type Status indicating LEDs Power on Green Protection Yellow Fault Red Ambient temperature Storage 25 C to 70 C 13 F to 158 F Operation 25 C to 60 C 13 F to 140 F Degree of protection IP66 UL app...

Page 23: ...200 355 450 370 640 PSTX370 690 70 200 257 355 355 450 600 370 640 PSTX30 370 Temp 40 C 104 oF 4 Ie in 10 sec Motor power when connected In Line Motor power when connected Inside Delta Full load curr...

Page 24: ...2 in 4x M6 1 4 in 1SFC132081M0201 Figure 10 Dimensions PSTX30 105 PSTX 142 170 1SFB536268G1011 1SFC132081M0201 11 220 mm 8 7 in 235 mm 9 3 in 377 mm 14 8 in 165 mm 6 5 in 7 5 mm 0 3 in 361 mm 14 2 in...

Page 25: ...51 mm 17 8 in 10 5 mm 0 4 in 389 mm 15 3 in 5 mm 0 2 in 151 mm 5 9 in M6 1 4 in 12 1SFC132081M0201 200 mm 7 9 in 258 mm 10 2 in 43 7 mm 1 7 in 4x 19 6 mm 0 8 in 6x Figure 12 Dimensions PSTX210 370 3 P...

Page 26: ...3 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 27: ...g 29 4 2 2 Minimum distance to wall front 29 4 2 3 Minimum enclosure size 30 4 2 4 Maximum mounting angle 30 4 2 5 Dimensions and drilling plan 30 4 2 6 Detachable keypad 30 4 2 6 1 Mounting Detachabl...

Page 28: ...at all items are included according to the delivery note See Table 1 Delivery note Check the softstarter as well as the packaging In case of damages please contact the transport company or the ABB res...

Page 29: ...f damage to property Ensure that no liquids dust or conductive parts enter the softstarter WARNING If you do not obey these instructions this can cause the softstarter to become overheated or not oper...

Page 30: ...drilling plan For dimensions and drilling plan see chapter 3 2 6 Dimensions Drilling plan is also printed on the box WARNING Risk of damage to property Ensure that no liquids drilling swarf dust or co...

Page 31: ...nnector through the drilled hole See 3 in Figure 21 Fasten the plastic screw nut on the threaded network connector with 2 Nm 17 7 lb in 3 Remove the RJ45 plug see 4 Connect one end of the network cabl...

Page 32: ...4 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 33: ...t and Stop terminals 13 14 18 19 20 21 37 5 1 2 4 Programmable inputs terminals 15 16 and 17 39 5 1 2 5 Programmable output relay K4 terminals 4 5 and 6 41 5 1 2 6 Programmable output relay K5 termina...

Page 34: ...een the softstarter and the motor since this can cause current peaks which can burn the thyristors in the softstarter If such capacitors are to be used they should be connected on the line side of the...

Page 35: ...Flexible 10 70 mm Rigid flexible 2x6 2x35 mm max 30 mm 1 181 in max 30 mm 1 181 in max 10 mm 0 394 in M10 28 Nm 240 lb in Using connection bars max 24 mm 0 945 in max 22 mm 0 866 in max 8 mm 0 315 in...

Page 36: ...PSTX370 should be earthed using the terminals as shown in Figure 27 one connection is sufficient Connect the cable to an earthing point close to the softstarter The cable should be as short as possib...

Page 37: ...x 0 6 mm 0 138 x 0 024 in M3 L 100 250V 50 60 Hz K4 K5 K6 Start Stop In0 In1 In2 GND 24V N 1SFC132081M0201 A conventional circuit with auxiliary relay is also possible See Figure 30 Tightening torque...

Page 38: ...5 mm2 AWG 12 24 0 5 Nm 4 3 lb in 3 5 x 0 6 mm 0 138 x 0 024 in M3 L 100 250V 50 60 Hz K4 K5 K6 Stop In0 In1 In2 GND 24V N 1SFC132081M0201 Tightening torques and cable dimensions 31 PSTX L 100 250V 50...

Page 39: ...0 5 Nm 4 3 lb in 3 5 x 0 6 mm 0 138 x 0 024 in M3 L 100 250V 50 60 Hz K4 K5 K6 Start Stop In0 In1 In2 GND 24V N 1SFC132081M0201 Tightening torques and cable dimensions 0 2 2 5 mm2 2x0 2 1 5 mm2 0 2 2...

Page 40: ...rminal 4 0 2 2 5 mm2 2x0 2 1 5 mm2 0 2 2 5 mm2 2x0 2 1 5 mm2 AWG 12 24 0 5 Nm 4 3 lb in 3 5 x 0 6 mm 0 138 x 0 024 in M3 L 100 250V 50 60 Hz K4 K5 K6 Start Stop In0 In1 In2 GND 24V N 1SFC132081M0201 T...

Page 41: ...sions 0 2 2 5 mm2 2x0 2 1 5 mm2 0 2 2 5 mm2 2x0 2 1 5 mm2 AWG 12 24 0 5 Nm 4 3 lb in 3 5 x 0 6 mm 0 138 x 0 024 in M3 5 L 100 250V 50 60 Hz K4 K5 K6 Start Stop In0 In1 In2 GND 24V N 1SFC132081M0201 5...

Page 42: ...esistance and the wire resistance are added together The resulting systematic errors must be taken into account when adjusting the tripping device A jumper must be connected between the terminals T2 a...

Page 43: ...ter and it shall refer to the functional ground The analogue output can be selected to show I A U V P kW P Hp Q kVAr S kVA cos Phi Motor temp SCR temp and Energy kWh If the analogue output is used the...

Page 44: ...5 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 45: ...dd information screens to Home view 52 6 3 2 2 Edit information screens in Home view 52 6 3 2 3 Display slot 52 6 3 2 4 Scale value range 53 6 3 3 Active faults protections and warnings 53 6 4 Menu sc...

Page 46: ...When softstarter is controlling operational voltage Ue during start or stop ramp Steady light When full operational volt age Ue is on at Top of Ramp Protection 3 Yellow Off When the softstarter has n...

Page 47: ...softstarter between local control from the HMI and remote control from hardwire input or fieldbus See 3 in Figure 46 i key The i key is an information key for the HMI and provides context related inf...

Page 48: ...vigation keys to select number the selected number is highlighted black Then Press or to change the value of the selected number Press Save to save See Figure 48 On off switch Select 1 or 0 on or off...

Page 49: ...1 2 Press Select to select Parameters menu 3 Press Select to select Complete list 4 Press Select to select 01 Motor rated current Ie 5 Press Edit to edit the rated current in Motor rated current Ie 6...

Page 50: ...long as Jog is pressed For intormation about Motor jog see chapter 6 2 4 Motor jog To reach the Motor Jog follow this path in menu Menu u Motor jog 6 2 1 Start key The start key is the start switch fo...

Page 51: ...ss Menu to enter the Motor jog menu and then select Motor Jog Use and to jog forward and backwards See 4 in Figure 53 The motor will start and accelerate to the rated speed according to the set parame...

Page 52: ...shown in the Home view Use the Navigation keys to change value Press Save to save the value Value is shown by 3 in Figure 55 6 3 Options screen 6 3 1 Overview In Options screen it is possible to chan...

Page 53: ...e Home view unit name See 4 in Figure 56 6 3 3 Active faults protections and warnings Path in menu Options u Active faults protections Options u Active warnings Active faults protections warnings are...

Page 54: ...Shows all parameters for advanced setup 6 4 1 2 Favorites Choose favorite parameter functions for quick selection 6 4 1 3 Modified Shows modified parameters Use Navigation keys to navigate in the subm...

Page 55: ...evel 28 06 Torque profile start 28 07 Torque finish 28 08 Torque tune 28 09 Torque ctrl gain 28 10 Torque PI intergration time 28 11 Torque slip 28 12 Torque diff 28 13 Torque filter time For full par...

Page 56: ...om defaults Press Select and then Edit to edit the parameter which differs from default Press Save to save and return to previous menu Or press Cancel to return to previous state without saving Figure...

Page 57: ...ssistants menu by pressing Menu and select Assistants with the Navigation keys Press Select to enter the Assistants menu Basic set up Use the Navigation keys to select Basic set up Press Select to ent...

Page 58: ...i key to see information about the Protection Press Back to return to Protections log menu Warnings Use the Navigation keys to select a Warning and press Details to read details about the Warning Nam...

Page 59: ...an store two backups Use the Navigation keys to select a earlier backup and press Replace to replace a backup 6 4 4 2 Uploading of parameters 1 After finishing the download of parameters detach the HM...

Page 60: ...aults Home view layout Will be available in a future release Reset fault log Reset all parameters Settings can be set with Keypad and Fieldbus communication HMI Softstarter Softstarter FW version 1 11...

Page 61: ...nu The icon symbols a wrench 3 Press the Select to enter the Settings menu 4 Highlight the first alternative and press Select and then Edit to enter Language settings 5 Use and to select language See...

Page 62: ...ay settings For navigation see Figure 75 The Display settings includes all display configurations of the softstarter To change the Display settings Press Edit to enter the setting level Press Save to...

Page 63: ...to select the data which is to be reset 4 Press Yes to reset or press No to cancel Confirmation of reset will be displayed as Done on the display Reset operating data Reset operating data is divided...

Page 64: ...6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 65: ...urrent limit 75 7 7 Kick start 76 7 8 Slow speed 77 7 9 Motor heating 78 7 10 Sequence start 79 7 11 Automatic restart 80 7 12 Inputs outputs 81 7 12 1 Digital inputs DI 82 7 12 2 Relay outputs 84 7 1...

Page 66: ...parameters Set the parameters via HMI With the HMI Keypad parameters can be set as individual parameter settings or as a selection of predefined parameters for different applications The HMI complete...

Page 67: ...rt a motor by controlling the output voltage or torque The Start ramp ends and goes into Top of ramp state when the output voltage reaches 100 voltage Settable start functions are Voltage start ramp T...

Page 68: ...r Motor Current Ie is configured with the following parameters Parameter Description Setting range Default value 01 01 Motor Current Ie Set the nominal current of the motor For good performance it is...

Page 69: ...l to full voltage The actual time to reach the Top of ramp state also depends on the current which means that the time to reach Top of ramp can be longer than the set Voltage ramp time If the motor is...

Page 70: ...ers Parameter Description Setting range Default value 02 02 Stop mode Set to voltage ramp No ramp Voltage ramp Torque ramp DC Brake Soft brake No ramp 02 05 Stop ramp end level Sets the level from whe...

Page 71: ...amp start the rotational speed is constant if the set torque curve corresponds to the actual load curve The output voltage will not increase linearly as when using the voltage start ramp see Figure 80...

Page 72: ...level from where the start ramp initiates 10 99 30 02 04 Start ramp time Sets the time it takes for the voltage to reach 100 1 120s 10s 03 05 Torque limit level Sets the limit for the torque during s...

Page 73: ...takes for the voltage to reach end level 1 120 s 10 s 28 05 Step down level Sets the level from where the stop ramp initiates 10 100 80 28 07 Torque finish Sets the operational torque for Torque star...

Page 74: ...tion Setting range Default value 02 02 Stop mode Set to No ramp No ramp Voltage stop ramp Torque stop ramp Voltage ramp 7 5 Stand still brake The Stand still brake breakes the output to the motor and...

Page 75: ...nt reaches the second current limit the softstarter will behave as for the normal current limit Dual current limit can be used as a back up function to prevent overheating Ramp current limit When the...

Page 76: ...the following parameters Parameter Description Setting range Default value 04 01 Kick start Enables a voltage peak at the beginning of the start ramp On Off Off 04 02 Kick start level Sets the level o...

Page 77: ...ltage applied to the motor and the motor stops For navigation see chapter 6 2 4 Motor Jog Slow speed is configured with the following parameters Parameter Description Setting range Default value 02 07...

Page 78: ...up the engine without starting it Motor heating is configured with the following parameters Parameter Description Setting range Default value 02 07 Pre start function Set to Motor heating Off Motor h...

Page 79: ...age start ramp Torque start ramp Full voltage ramp Voltage start ramp 08 04 Start ramp time seq 1 08 32 seq 2 08 62 seq 3 Sets the time it takes for the voltage to reach 100 1 120 s 10 s 08 05 Start r...

Page 80: ...with a fixed time interval between each During the time between each restart the start digital input signal is ignored If the fault still remain by the time a restart is made this will be seen as a fa...

Page 81: ...ay output 1 Analog output To use an extension IO provides the same possibilities to use all the softstarters functions as for the programmable internal IO Available Extension IO TBD For example an Ext...

Page 82: ...reverse While the digital input is high the motor will slowly move in the reverse direction Motor heating While the digital input is high the motor heating is active Stand still brake While the digit...

Page 83: ...rse User defined protection Emergency mode Fieldbus disable control Start 1 Start 2 Start 3 Reset 10 02 In1 function Same as In0 None 10 03 In2 function Same as In0 None External digital Inputs extens...

Page 84: ...t is continuously shorted to common Internal relay outputs internal IO is configured with the following parameters Parameter Description Setting range Default value 10 04 K4 function Function of progr...

Page 85: ...rrent output can be set by a configuration parameter AO reference in the softstarter The selection of voltage or current must be set to adapt to the analog meter or the PLC The settings are 0 10V volt...

Page 86: ...e Sets the min analog output value 0 0 1000000 0 External Analog output Extension IO is configured with the following parameters Description Description Setting range Default value 11 13 1AO0 referenc...

Page 87: ...100 The softstarter has a 3 wire PT100 input that can be combined and share terminals with the PTC input The trip temperature is set by the user The maximum trip temperature is 250 and lowest is 25 Th...

Page 88: ...ation the fieldbus interface must be enabled before any action can be taken Fieldbus address If the softstarter is going to be used with fieldbus communication set a fieldbus address for the softstart...

Page 89: ...which baudrates that can be used for different protocols See separate Table below 12 10 FB parity Sets parity for Anybus Modbus RTU No parity Odd parity Even parity Even parity 12 11 FB stop bits Sele...

Page 90: ...3 Sets the AI 3 programmable analog input signal Phase L3 current 12 25 Fieldbus AI 4 Sets the AI 4 programmable analog input signal Max phase curent 12 26 Fieldbus AI 5 Sets the AI 5 programmable an...

Page 91: ...can be mapped to a relay output or and a fieldbus signal For each supervision function there is a parameter for assigning the corresponding event to one or more Event groups In PSTX there are seven E...

Page 92: ...ion is activated When any of the protections signals a risk of damage the following basic actions will be performed Protection LED will light up The type of event is displayed The type of event is log...

Page 93: ...ction is configured with the following parameters Parameter Description Setting range Default value 13 06 Locked rotor level Set the locked rotor trip level 0 5 8 0 x Ie 4 0 x Ie 13 07 Locked rotor tr...

Page 94: ...s the operation of this protection Off Stop manual Stop auto Indication Off 7 15 5 Power factor underload protection The power factor has fallen below the normal level The Power factor underload prote...

Page 95: ...rational in the Standby state Over voltage protection is configured with the following parameters Parameter Description Setting range Default value 15 01 Over voltage level Sets the Over voltage trip...

Page 96: ...his protection detects if the phases are connected in the wrong order and then prevents the engine from starting Check the phase sequence on the line side to L1 L2 L3 Phase reversal protection is conf...

Page 97: ...protection belongs to Eventgroup 0 6 2 16 11 Voltage outputs op Sets the operation of this protection Off Stop manual Stop auto Indication Off 7 15 14 Temperature sensors 7 15 14 1 External thermal se...

Page 98: ...Sets the PT100 reset temperature 50 250 40 17 06 PT100 out Specifies the Event groups this protection belongs to Eventgroup 0 6 2 17 07 PT100 op Sets the operation of this protection Off Stop manual S...

Page 99: ...r the set current limit Check starting conditions and parameters Too long current limit protection is configured with the following parameters Parameter Description Setting range Default value 18 08 T...

Page 100: ...up 0 6 2 19 04 Fieldbus failure op Sets the operation of this protection Off Stop manual Stop auto Indication Off 7 15 20 Extension IO failure protection This protection detacts if there is communicat...

Page 101: ...warning A warning signal will be given if the motor temperature exceeds the settable warning level of max temperature Electronic overload warning is configured with the following parameters Parameter...

Page 102: ...1 0 x Ie 0 4 x Ie 21 02 Curr underload trip time Sets the time that the current has to be under the Warning level to trip 0 30 s 5 s 21 03 Curr underload delay time Sets the time delay after Top of r...

Page 103: ...range Default value 22 01 Over voltage level User configured warning level in Volts 208 850 V 208 V 22 02 Over voltage trip time User configured time until warning in seconds 0 1 100 0 s 1 0 s 22 03 O...

Page 104: ...ription Setting range Default value 23 01 EOL time to trip time Sets how long time before the EOL protection trips the warning is activated 1 1000 s 5 s 23 02 EOL time to trip out Specifies the Event...

Page 105: ...umber of starts out Specifies the Event groups this warning belongs to Eventgroup 0 6 4 24 03 Number of starts Enables Number of starts limits warning level Off On Off 7 16 14 Fans fault warning A war...

Page 106: ...ults are detected these basic actions will be performed Fault LED will light up The type of event is displayed The type of event is logged on the event list Faults cannot be configured in other way th...

Page 107: ...o a direct stop If the the Fire pump is enabled and a fault is detected the softstarter will try to run the motor according to the start and stop signals ignore safety and continue to run regardless o...

Page 108: ...ge Default value 25 05 Open circuit thyr out Specifies the Event groups this fault belongs to Eventgroup 0 6 1 25 06 Open circuit thyr out Sets the operation of this fault Stop manual Stop auto Stop m...

Page 109: ...Heat sink over temp op Sets the operation of this fault Stop manual Stop auto Stop manual 7 17 1 6 Unspecified fault This fault is a grouping of several internal faults that are quite unlikely and do...

Page 110: ...ongs to Eventgroup 0 6 1 26 04 Bad network op Set the operation of this fault Stop manual Stop auto Stop manual 7 17 2 3 Low supply voltage fault Too low control supply voltage on terminals 1 and 2 A...

Page 111: ...eed functions and the motor is connected inside delta Faulty usage fault is configured with the following parameters Parameter Description Setting range Default value 26 09 Faulty usage out Specifies...

Page 112: ...the time between start signal and beginning of diagnostic measurements 0 65535 ms 245 ms 7 18 4 TOR relay delay time TBD TOR relay delay time is configured with the following parameters Parameter Desc...

Page 113: ...ng voltage ramp it shall be set to 80 Depending on the load it can be necessary to adjust the step down level Step down level is configured with the following parameters Parameter Description Setting...

Page 114: ...on should not be selected again If this is done all the tuning will be reset to the default settings for the selected application Enter the Assistants menu Find the Assistants menu by pressing right S...

Page 115: ...pump 10 10 40 30 4 5 Voltage ramp Torque ramp Hydraulic pump 10 30 30 3 Voltage ramp No ramp Lift Elevator 10 30 30 3 5 Voltage ramp No ramp Piston compressor 5 50 30 3 Voltage ramp No ramp Scroll co...

Page 116: ...orward Fast jog Jog Creep 0 0 Jog 05 02 Slow speed fwd strenght 10 100 0 0 50 05 03 Slow speed reverse Fast jog Jog Creep 0 0 Jog 05 04 Slow speed rev strength 10 100 0 0 50 06 Motor heating 06 01 Mot...

Page 117: ...defined protection Emergency mode Fieldbus disable control Start 1 Start 2 Start 3 0 130 Reset 10 02 In1 function 0 15 0 131 None 10 03 In2 function 0 15 0 132 None 10 04 K4 function None Run Top of r...

Page 118: ...O2 function 0 15 0 155 None 11 12 2DO3 function 0 15 0 156 None 11 13 1AO0 reference 0 10 mA 0 20 mA 4 20 mA 0 10 V 0 157 4 20 mA 11 14 1AO0 type Motor current A Mains voltage V Active power kW Active...

Page 119: ...5 Event group 3 status 12 20 Fieldbus DI 9 0 32 0 166 Event group 4 status 12 21 Fieldbus DI 10 0 32 0 167 Event group 5 status 12 22 Fieldbus AI 1 None Phase L1 current Phase L2 current Active power...

Page 120: ...factor underload op Off Stop Manual Stop Automatic Indication 0 0 Off 14 11 Curr imb level 10 80 0 61 80 14 12 Curr imb trip time 1 30 s 0 63 10 s 14 13 Curr imb delay time 1 30 s 0 62 30 s 14 14 Curr...

Page 121: ...19 01 HMI failure out 0 127 0 100 0000010 19 02 HMI failure op Off Stop Manual Stop Automatic Indication Switch of HMI control 0 0 Off 19 03 Fieldbus failure out 0 127 0 97 0000010 19 04 Fieldbus fai...

Page 122: ...Shunt fault op Stop Manual Stop Automatic 0 0 Stop Manual 25 03 Short circuit out 0 127 0 50 0000001 25 04 Short circuit fault op Stop Manual Stop Automatic 0 0 Stop Manual 25 05 Open circuit thyr ou...

Page 123: ...ss trip angle 1 1 240 0 12 28 26 Phase loss trip angle 2 1 240 0 0 70 28 27 Bad network quality On Off 0 35 On 28 28 Low supply voltage On Off 0 37 On 28 29 High current fault On Off 0 38 On 28 30 Shu...

Page 124: ...7 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 125: ...1 Instructions 126 8 2 2 Required accessories 126 8 3 ABB Fieldbus plug interface option 126 8 3 1 Instructions 126 8 3 2 Required accessories 126 8 4 Mini USB interface 127 8 Communication Phone 800...

Page 126: ...cting the ABB Fieldbus Plug Adapter FBPA used for fieldbus communication With this interface it is possible to control the softstarter retreive status information as well as upload and download parame...

Page 127: ...s PCs The USB interface is located on the front of the detachable HMI With this interface it is possible to control the softstarter retreive status information as well as upload and download parameter...

Page 128: ...8 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 129: ...9 9 1 Regular maintenance 130 9 2 Service and repair 130 9 Maintenance Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 130: ...nce This can be checked at voltage free state Check the Real Time Clock and adjust if necessary In case of a fault or if a fault can not be reset see chapter 10 9 2 Service and repair In case the PSTX...

Page 131: ...9 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 132: ...9 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 133: ...10 3 Overview of faults protections and warnings 137 10 4 Protection indication shown on screen 138 10 5 Fault indication shown on screen 139 10 6 Warning indication shown on screen 141 Phone 800 894...

Page 134: ...so be found in this chapter 10 2 Troubleshooting Table 1 Troubleshooting Status Possible cause Solution Motor humming starts without given start signal By pass relay closed due to inaccurate handling...

Page 135: ...al control mode Check connections for start and stop Check that start and stop command is not given at the same time Check that the keypad is not in Local Control mode Press the R L key to change to R...

Page 136: ...otor current Inside Delta connection If the softstarter is connected Inside Delta the phase currents displayed are 58 1 3 of the motor current Displayed current in screen is not stable The motor is to...

Page 137: ...lure protection X X X X X X X X X X Extension IO failure protection X X X X X X X X X X HMI failure protection X X X X X X X X X X Limit number of starts X Faults Phase loss fault X X X X X X X X High...

Page 138: ...rt the motor and check the main currents and voltage Current imbalance protection Current imbalance between the phases Restart the motor and check the main currents and voltage Over voltage protection...

Page 139: ...n removed Place back the HMI again Limit number of starts The softstarter has exceeded the pre set limited number of starts Wait for the next start interval For parameter setting see chapter 7 Functio...

Page 140: ...on operational voltage on terminals L1 L2 and L3 If same fault remains contact your ABB Sales Office Unspecified fault N A Disconnect and reconnect the supply voltage Us and make a restart If same fau...

Page 141: ...ctor underload warning The power factor has decreased below the adjustable value during continuous operation Current underload warning The motor current has fallen below the warning level Check that t...

Page 142: ...10 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 143: ...ams 11 1 Circuit diagram PSTX 144 11 1 3 Circuit diagram PSTX30 PSTX170 IEC version 144 11 1 4 Circuit diagram PSTX30 PSTX170 UL version 144 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Emai...

Page 144: ...T1 4T2 6T3 1L1 3L2 5L3 V5 V6 K2 V4 V3 V2 V1 Ct1 Ct2 Ct3 2 T1 1 L1 11 1 4 Circuit diagram PSTX30 PSTX170 UL version CAUTION Terminal 22 is a function earth it is not a protective earth It shall be conn...

Page 145: ...11 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Page 146: ...isions is done on this document Document number Revision Chapter Description Date 1SFC132081M0201 A First release 2014 06 27 12 12 Revisions Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Emai...

Reviews: