State
K2 LED
K1 LED
IN1/2 LED
PWR LED
The sensor circuit is active. All relays are picked up.
ON
ON
ON
ON
Possible error, see the data sheet of the relay.
Other LED combination
For more information, see the data sheet of the relay (
For more fault tracing possibilities, see the hardware and firmware manuals of the drive.
■
ACS880-07LC/17LC/37LC drives and ACS880 multidrives with option
+Q951+Q984
The type of the emergency stop safety relay [A61] is DOLD LG 5925.
This table gives the indications of the DOLD LG 5925 relay:
LED is off
LED is on
LED
Power supply is not connected, or there is an
external error.
Power supply is connected.
Netz
There is an external error.
Relay K1 is energized.
K1
There is an external error.
Relay K2 is energized.
K2
For more information, see the data sheet of the relay (
For more fault tracing possibilities, see the hardware and firmware manuals of the drive.
■
ACS880-07LC/17LC/37LC drives and ACS880 multidrives with option
+Q952+Q984
The type of the emergency stop safety relay [A61] is DOLD UG 6960.
This table gives the indications of the DOLD UG 6960 relay:
LED is off
LED is flashing
LED is on
Color
LED
Power supply is not connec-
ted.
-
Power supply is connected.
Green
ON
-
When flashing in 1:1 rela-
tion: Power supply under-
voltage or overvoltage.
System error. Replace the
unit if the error is not re-
moved after restart.
Red
ERR
When flashing in 4:1 rela-
tion: There is an external er-
ror.
-
There is an external error.
See the figure below for the
indications of the LED.
Relays K1 and K2 are ener-
gized (instantaneous con-
tact).
Green
K1/K2
-
During the time delay.
Relays K3 and K4 are ener-
gized (delayed contacts).
Green
K3/K4
48 Fault tracing