26
CURRENT TRANSFORMER CONNECTIONS
600:5 MULTI-RATIO
1200:5 MULTI-RATIO
CURRENT TRANSFORMER
CURRENT TRANSFORMER
TERMINAL
RATIO
TERMINAL
RATIO
X2-X3
50-5
X2-X3
100-5
X1-X2
100-5
X1-X1
200-5
X1-X3
150-5
X1-X3
300-5
X4-X5
200-5
X4-X5
400-5
X3-X4
250-5
X3-X4
500-5
X2-X4
300-5
X2-X4
600-5
X1-X4
400-5
X1-X4
800-5
X3-X5
450-5
X3-X5
900-5
X2-X5
500-5
X2-X5
1000-5
X1-X5
600-5
X1-X5
1200-5
2000:5 MULTI-RATIO
3000:5 MULTI-RATIO
CURRENT TRANSFORMER
CURRENT TRANSFORMER
TERMINAL
RATIO
TERMINAL
RATIO
X3-X4
300-5
X3-X4
300-5
X1-X2
400-5
X4-X5
500-5
X4-X5
500-5
X3-X5
800-5
X2-X3
800-5
X1-X2
1000-5
X2-X4
1100-5
X2-X3
1200-5
X1-X3
1200-5
X2-X4
1500-5
X1-X4
1500-5
X2-X5
2000-5
X2-X5
1600-5
X1-X3
2200-5
X1-X5
2000-5
X1-X4
2500-5
X1-X5
3000-5
VOLTS
NON INDUCTIVE CIRCUITS
INDUCTIVE CIRCUITS
CONTINUOUS
MAKE AND BREAK (A)
MAKE AND BREAK (A)
RATING (A)
24/48 VDC
16
16
20
125 VDC
10
10
20
250 VDC
5
5
20
115 VAC
15
15
20
230 VAC
10
10
20
AUXILIARY SWITCH CURRENT SPECIFICATIONS
• Tested per UL Document 1054. AC tests specs with one set of contacts. DC tests specs with
two sets of contacts in series.
• Contacts will carry 140 A for 3 seconds.
• Overload test – 50 operations at 90 A and 120 VAC.
Summary of Contents for R-MAG
Page 12: ...Figure 3 Interrupter Assembly 15 5 kV 1250 A 12 ...
Page 13: ...Figure 4 Interrupter Assembly 15 5 kV 2000 A 13 ...
Page 14: ...Figure 5 Interrupter Assembly 15 5 kV 3000 A 3700 FA 14 ...
Page 15: ...Figure 6 Interrupter Assembly 27 kV 1250 A 15 ...
Page 16: ...Figure 7 Interrupter Assembly 27 kV 2000 A 16 ...
Page 19: ...19 Figure 11 High Voltage Cabinet Layout 15 5 and 27 kV ...
Page 20: ...20 Figure 12 Typical Schematic Diagram ...
Page 21: ...Figure 13 Standard ED2 0 Circuit Board 21 ...
Page 22: ...22 Figure 14 Typical Outline 15 5 kV 1250 A ...
Page 23: ...23 Figure 15 Typical Outline 15 5 kV 2000 3000 3700 A and 27 kV 1250 2000 A ...
Page 40: ...40 9 0 TROUBLESHOOTING FLOWCHARTS ILLUSTRATION 5 READY LED CONTINUALLY FLASHING ...
Page 41: ...41 ILLUSTRATION 6 READY LED OFF ...
Page 42: ...42 ILLUSTRATION 7 CB WILL EITHER NOT OPEN OR CLOSE ...
Page 50: ...NOTES 50 ...
Page 51: ...NOTES 51 ...