M12760-1 v9.1.1
Table 63. Disturbance report DRPRDRE
Function
Range or value
Accuracy
Pre-fault time
(0.05–9.90) s
-
Post-fault time
(0.1–10.0) s
-
Limit time
(0.5–10.0) s
-
Maximum number of recordings
100, first in - first out
-
Time tagging resolution
1 ms
See table
Maximum number of analog inputs
30 + 10 (ex internally
derived)
-
Maximum number of binary inputs
128
-
Maximum number of phasors in the Trip Value recorder per recording
30
-
Maximum number of indications in a disturbance report
96
-
Maximum number of events in the Event recording per recording
150
-
Maximum number of events in the Event list
1000, first in - first out
-
Maximum total recording time (3.4 s recording time and maximum number of
channels, typical value)
340 seconds (100 recordings) at
50 Hz, 280 seconds (80
recordings) at 60 Hz
-
Sampling rate
1 kHz at 50 Hz
1.2 kHz at 60 Hz
-
Recording bandwidth
(5-300) Hz
-
GUID-F034B396-6600-49EF-B0A5-8ED96766A6A0 v6
Table 64. Insulation gas monitoring function SSIMG
Function
Range or value
Accuracy
Pressure alarm level
1.00-100.00
±10.0% of set value
Pressure lockout level
1.00-100.00
±10.0% of set value
Temperature alarm level
-40.00-200.00
±2.5% of set value
Temperature lockout level
-40.00-200.00
±2.5% of set value
Time delay for pressure alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is greater
Reset time delay for pressure alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is greater
Time delay for pressure lockout
(0.000-60.000) s
±0.2% or ±250ms whichever is greater
Time delay for temperature alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is greater
Reset time delay for temperature alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is greater
Time delay for temperature lockout
(0.000-60.000) s
±0.2% or ±250ms whichever is greater
1MRK 505 362-BEN B
Busbar protection REB650 2.1 IEC
Product version: 2.1
46
ABB