IEC 60870-5-103 communication protocol
SEMOD120137-5 v3
A single glass or plastic port is provided for the IEC
60870-5-103 standard. This allows design of simple
substation automation systems including equipment from
different vendors. Disturbance files uploading is provided.
DNP3.0 communication protocol
SEMOD153688-5 v1
An electrical RS485 and an optical Ethernet port is available
for the DNP3.0 communication. DNP3.0 Level 2
communication with unsolicited events, time synchronizing
and disturbance reporting is provided for communication to
RTUs, Gateways or HMI systems.
Multiple command and transmit
M14791-3 v3
When IEDs are used in Substation Automation systems with
LON, SPA or IEC 60870-5-103 communication protocols, the
Event and Multiple Command function blocks are used as the
communication interface for vertical communication to station
HMI and gateway, and as interface for horizontal peer-to-peer
communication (over LON only).
IEC 62439-3 Parallel Redundancy Protocol
GUID-A90FDBA7-D4D7-4CBD-9F05-13DCC9971779 v5
Redundant station bus communication according to IEC
62439-3 Edition 1 and IEC 62439-3 Edition 2 parallel
redundancy protocol (PRP) are available as options when
ordering IEDs. Redundant station bus communication
according to IEC 62439-3 uses both port AB and port CD on
the OEM module.
14. Hardware description
Hardware modules
IP14529-1 v1
Power supply module PSM
M11595-3 v5
The power supply module is used to provide the correct
internal voltages and full isolation between the IED and the
battery system. An internal fail alarm output is available.
Binary input module BIM
M1769-3 v4
The binary input module has 16 optically isolated inputs and
is available in two versions, one standard and one with
enhanced pulse counting capabilities on the inputs to be
used with the pulse counter function. The binary inputs are
freely programmable and can be used for the input of logical
signals to any of the functions. They can also be included in
the disturbance recording and event-recording functions. This
enables extensive monitoring and evaluation of operation of
the IED and for all associated electrical circuits.
Binary output module BOM
M6938-3 v4
The binary output module has 24 independent output relays
and is used for trip output or any signaling purpose.
Binary input/output module IOM
M6939-3 v6
The binary input/output module is used when only a few input
and output channels are needed. The ten standard output
channels are used for trip output or any signaling purpose.
The two high speed signal output channels are used for
applications where short operating time is essential. Eight
optically isolated binary inputs cater for required binary input
information.
Optical ethernet module OEM
M16073-3 v6
The optical fast-ethernet module is used for fast and
interference-free communication of synchrophasor data over
IEEE C37.118 and/or IEEE 1344 protocols. It is also used to
connect an IED to the communication buses (like the station
bus) that use the IEC 61850-8-1 protocol (port A, B). The
module has one or two optical ports with ST connectors.
Serial and LON communication module SLM, supports
SPA/IEC 60870-5-103, LON and DNP 3.0
M14933-3 v4
The serial and LON communication module (SLM) is used for
SPA, IEC 60870-5-103, DNP3 and LON communication. The
module has two optical communication ports for plastic/
plastic, plastic/glass or glass/glass. One port is used for serial
communication (SPA, IEC 60870-5-103 and DNP3 port) and
one port is dedicated for LON communication.
Galvanic RS485 serial communication module
SEMOD158664-5 v3
The Galvanic RS485 communication module (RS485) is used
for DNP3.0 and IEC 60870-5-103 communication. The
module has one RS485 communication port. The RS485 is a
balanced serial communication that can be used either in 2-
wire or 4-wire connections. A 2-wire connection uses the
same signal for RX and TX and is a multidrop communication
with no dedicated Master or slave. This variant requires
however a control of the output. The 4-wire connection has
separated signals for RX and TX multidrop communication
with a dedicated Master and the rest are slaves. No special
control signal is needed in this case.
IRIG-B Time synchronizing module
SEMOD141113-4 v7
The IRIG-B time synchronizing module is used for accurate
time synchronizing of the IED from a station clock.
Electrical (BNC) and optical connection (ST) for 0XX and 12X
IRIG-B support.
Transformer input module TRM
M14875-3 v9
The transformer input module is used to galvanically separate
and adapt the secondary currents and voltages generated by
the measuring transformers. The module has twelve inputs in
different combinations of currents and voltage inputs.
Alternative connectors of Ring lug or Compression type can
be ordered.
High impedance resistor unit
M16727-3 v2
The high impedance resistor unit, with resistors for pick-up
value setting and a voltage dependent resistor, is available in
a single phase unit and a three phase unit. Both are mounted
on a 1/1 19 inch apparatus plate with compression type
terminals.