16. Technical data
General
IP11376-1 v2
M10993-1 v3
Definitions
Reference value
The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range
The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements
Operative range
The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements
Energizing quantities, rated values and limits
IP15765-1 v2
Analog inputs
IP15842-1 v1
M16988-1 v10
Table 5. TRM - Energizing quantities, rated values and limits for protection transformer modules
Quantity
Rated value
Nominal range
Current
I
r
= 1 or 5 A
(0.2-40) × I
r
Operative range
(0-100) x I
r
Permissive overload
4 × I
r
cont.
100 × I
r
for 1 s
*)
Burden
< 150 mVA at I
r
= 5 A
< 20 mVA at I
r
= 1 A
AC voltage
U
r
= 110 V
0.5–288 V
Operative range
(0–340) V
Permissive overload
420 V cont.
450 V 10 s
Burden
< 20 mVA at 110 V
Frequency
f
r
= 50/60 Hz
±5%
*)
max. 350 A for 1 s when COMBITEST test switch is included.
SEMOD55310-2 v9
Table 6. OEM - Optical ethernet module
Quantity
Rated value
Number of channels
1 or 2 (port A, B for IEC 61850-8-1 / IEEE C37.118)
Standard
IEEE 802.3u 100BASE-FX
Type of fiber
62.5/125
m
m multimode fibre
Wave length
1300 nm
Optical connector
Type ST
Communication speed
Fast Ethernet 100 Mbit/s
1MRK 505 362-BEN B
Busbar protection REB650 2.1 IEC
Product version: 2.1
ABB
23