example, in the case of the protection of a transformer that might be overexcited.
The time delay must be co-ordinated with other automated actions in the system.
tResetn
: Reset time for step
n
if definite time delay is used, given in s. The default
value is 25 ms.
tnMin
: Minimum operation time for inverse time characteristic for step
n
, given in
s. For very high voltages the overvoltage function, using inverse time
characteristic, can give very short operation time. This might lead to unselective
trip. By setting
t1Min
longer than the operation time for other protections such
unselective tripping can be avoided.
ResetTypeCrvn
: Set reset type curve for step
n
. This parameter can be set:
Instantaneous
,
Frozen time
,
Linearly decreased
. The default setting is
Instantaneous
.
tIResetn
: Reset time for step
n
if inverse time delay is used, given in s. The default
value is 25 ms.
kn
: Time multiplier for inverse time characteristic. This parameter is used for co-
ordination between different inverse time delayed undervoltage protections.
ACrvn
,
BCrvn
,
CCrvn
,
DCrvn
,
PCrvn
: Parameters for step
n
, to set to create
programmable undervoltage inverse time characteristic. Description of this can be
found in the technical reference manual.
CrvSatn
: Set tuning parameter for step
n
. When the denominator in the expression
of the programmable curve is equal to zero, the time delay will be infinite. There
will be an undesired discontinuity. Therefore, a tuning parameter
CrvSatn
is set to
compensate for this phenomenon. In the voltage interval
U>
up to
U>
· (1.0 +
CrvSatn
/100) the used voltage will be:
U>
· (1.0 +
CrvSatn
/100). If the
programmable curve is used this parameter must be calculated so that:
0
100
CrvSatn
B
C
×
- >
EQUATION1448 V1 EN-US
(Equation 35)
HystAbsn:
Absolute hysteresis for step
n
, set in % of
UBase
. The setting of this
parameter is highly dependent of the application. The hysteresis is used to avoid
oscillations of the START output signal. This signal resets when the measured
voltage drops below the setting level and leaves the hysteresis area. Make sure that
the set value for parameter
HystABSn
is somewhat smaller than the set pickup
value. Otherwise there is a risk that step n will not reset properly.
1MRK 505 388-UEN B
Section 8
Voltage protection
Busbar protection REB650 2.2 IEC
143
Application manual
Summary of Contents for REB650
Page 1: ...RELION 650 SERIES Busbar protection REB650 Version 2 2 Application manual...
Page 2: ......
Page 18: ...12...
Page 28: ...22...
Page 38: ...32...
Page 78: ...72...
Page 96: ...90...
Page 136: ...130...
Page 150: ...144...
Page 156: ...150...
Page 232: ...226...
Page 278: ...272...
Page 298: ...292...
Page 310: ...304...
Page 320: ...314...
Page 321: ...315...