10.7.3
Setting guidelines
M12448-3 v2
The parameters for Single command, 16 signals (SINGLECMD) are set via the
local HMI or PCM600.
Parameters to be set are MODE, common for the whole block, and CMDOUTy
which includes the user defined name for each output signal. The MODE input sets
the outputs to be one of the types Off, Steady, or Pulse.
•
Off, sets all outputs to 0, independent of the values sent from the station level,
that is, the operator station or remote-control gateway.
•
Steady, sets the outputs to a steady signal 0 or 1, depending on the values sent
from the station level.
•
Pulse, gives a pulse with 100 ms duration, if a value sent from the station level
is changed from 0 to 1. That means the configured logic connected to the
command function block may not have a cycle time longer than the cycle time
for the command function block.
Section 10
1MRK 505 388-UEN B
Control
174
Busbar protection REB650 2.2 IEC
Application manual