OperLOLevel
: Lockout limit for number of mechanical operations.
CurrExponent
: Current exponent setting for energy calculation. It varies for
different types of circuit breakers. This factor ranges from
0.5
to
3.0
.
AccStopCurr
: RMS current setting below which calculation of energy
accumulation stops. It is given as a percentage of
IBase
.
ContTrCorr
: Correction factor for time difference in auxiliary and main contacts'
opening time.
AlmAccCurrPwr
: Setting of alarm level for accumulated energy.
LOAccCurrPwr
: Lockout limit setting for accumulated energy.
SpChAlmTime
: Time delay for spring charging time alarm.
tDGasPresAlm
: Time delay for gas pressure alarm.
tDGasPresLO
: Time delay for gas pressure lockout.
DirCoef
: Directional coefficient for circuit breaker life calculation.
RatedOperCurr
: Rated operating current of the circuit breaker.
RatedFltCurr
: Rated fault current of the circuit breaker.
OperNoRated
: Number of operations possible at rated current.
OperNoFault
: Number of operations possible at rated fault current.
CBLifeAlmLevel
: Alarm level for circuit breaker remaining life.
AccSelCal
: Selection between the method of calculation of accumulated energy.
OperTimeDelay
: Time delay between change of status of trip output and start of
main contact separation.
12.5
Event function EVENT
IP14590-1 v2
12.5.1
Identification
SEMOD167950-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event function
EVENT
S00946 V1 EN-US
-
Section 12
1MRK 505 388-UEN B
Monitoring
214
Busbar protection REB650 2.2 IEC
Application manual
Summary of Contents for REB650
Page 1: ...RELION 650 SERIES Busbar protection REB650 Version 2 2 Application manual...
Page 2: ......
Page 18: ...12...
Page 28: ...22...
Page 38: ...32...
Page 78: ...72...
Page 96: ...90...
Page 136: ...130...
Page 150: ...144...
Page 156: ...150...
Page 232: ...226...
Page 278: ...272...
Page 298: ...292...
Page 310: ...304...
Page 320: ...314...
Page 321: ...315...