Figure 76:
High-availability Seamless Redundancy (HSR)
14.2.3
Setting guidelines
GUID-887B0AE2-0F2E-414D-96FD-7EC935C5D2D8 v1
Redundant communication is configured with the Ethernet configuration tool in
PCM600.
Redundancy
: redundant communication is activated when the parameter is set to
PRP-0
,
PRP-1
or
HSR
. The settings for the next access point will be hidden and
PhyPortB will show the second port information. Redundant communication is
activated after a common write to IED is done.
PRP-1
should be used primarily,
PRP-0
is intended only for use in existing PRP-
networks. PRP-1 and HSR can be combined in a mixed network.
If the access point is not taken into operation, the write option in Ethernet
Configuration Tool can be used to activate the access point.
Section 14
1MRK 505 388-UEN B
Ethernet-based communication
234
Busbar protection REB650 2.2 IEC
Application manual