GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN
GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN-US
Figure 95:
Settings for IEC 60870-5-103 communication
The general settings for IEC 60870-5-103 communication are the following:
•
SlaveAddress
and
BaudRate
: Settings for slave number and communication
speed (baud rate).
The slave number can be set to any value between 1 and 254. The
communication speed, can be set either to 9600 bits/s or 19200 bits/s.
•
RevPolarity
: Setting for inverting the light (or not). Standard IEC 60870-5-103
setting is
On
.
•
CycMeasRepTime
: See I103MEAS function block for more information.
•
EventRepMode
: Defines the mode for how events are reported. The event
buffer size is 1000 events.
Event reporting mode
If
EventRepMode
=
SeqOfEvent
, all GI and spontaneous events will be delivered in
the order they were generated by BSW. The most recent value is the latest value
delivered. All GI data from a single block will come from the same cycle.
If
EventRepMode
=
HiPriSpont
, spontaneous events will be delivered prior to GI
event. To prevent old GI data from being delivered after a new spontaneous event,
the pending GI event is modified to contain the same value as the spontaneous
event. As a result, the GI dataset is not time-correlated.
15.6.2.2
Settings from PCM600
M17109-132 v2
I103USEDEF
GUID-A41170D6-2846-4E5E-8B7F-85B53D4EF6B6 v1
For each input of the I103USEDEF function there is a setting for the information
number of the connected signal. The information number can be set to any value
between 0 and 255. To get proper operation of the sequence of events the event
masks in the event function is to be set to ON_CHANGE. For single-command
signals, the event mask is to be set to ON_SET.
In addition there is a setting on each event block for function type. Refer to
description of the Main Function type set on the local HMI.
1MRK 505 388-UEN B
Section 15
Station communication
Busbar protection REB650 2.2 IEC
265
Application manual
Summary of Contents for REB650
Page 1: ...RELION 650 SERIES Busbar protection REB650 Version 2 2 Application manual...
Page 2: ......
Page 18: ...12...
Page 28: ...22...
Page 38: ...32...
Page 78: ...72...
Page 96: ...90...
Page 136: ...130...
Page 150: ...144...
Page 156: ...150...
Page 232: ...226...
Page 278: ...272...
Page 298: ...292...
Page 310: ...304...
Page 320: ...314...
Page 321: ...315...