Table 34: Dependencies between RetripMode and FunctionMode
RetripMode
FunctionMode
Description
Off
N/A
the re-trip function is disabled
UseFunctionMode
Current
a phase current must be larger
than the set operate level to allow
re-trip once the t1 timer elapses
CB Pos
Re-trip is done when breaker
position indicates that breaker is
still closed after re-trip time has
elapsed
Current or CB Pos
both methods are used
Always
N/A
Re-trip is always given when t1
elapses without any further
checks
IP>: Current level for detection of breaker failure, set in % of IBase. This parameter should be
set so that faults with small fault current can be detected. The setting can be chosen in
accordance with the most sensitive protection function to start the breaker failure protection.
Default setting is 10% of
IBase. Note that this setting shall not be set lower than 4% of Ir,
where Ir is rated current of the IED CT input where function is connected. In principle Ir is
either 1A or 5A depending on the ordered IED
I>BlkCont: If the FunctionMode is set to Current or CB pos breaker failure for high current
faults are safely detected by the current measurement function. To increase security for low
currents the contact based function will be enabled only if the current at the moment of
starting is below this set level. The setting can be given within the range 5 – 200% of
IBase. It
is strongly recommended to set this level above
IPh> set level.
t1: Time delay of the retrip. The setting can be given within the range 0 – 60s in steps of 0.001
s. Typical setting is within range 0 – 50ms.
t2: Time delay of the backup trip. The choice of this setting is made as short as possible at the
same time as unwanted operation must be avoided. Typical setting is 90 – 200ms (also
dependent of retrip timer).
The minimum time delay for the backup trip can be estimated as:
_
_
arg
2
1
CB open
BFP reset
m
in
t
t
t
t
t
EQUATION1430 V2 EN-US
(Equation 42)
where:
t
CB_open
is the maximum opening time for the circuit breaker
t
BFP_reset
is the maximum time for breaker failure protection to detect correct breaker function
(the current criteria reset)
t
margin
is a safety margin
It is often required that the total fault clearance time shall be less than a given critical time.
This time is often dependent of the ability to maintain transient stability in case of a fault
close to a power plant.
Section 7
1MRK 505 370-UEN D
Current protection
186
Busbar protection REB670
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...