Table 5. Software
Description
Value
Communication protocols
Via GPRS to and from
SCADA
IEC 60870-5-104
Via serial ports downward
IEC 60870-5-101 or transparent mode
Downward
Ethernet port
Network protocols
PPP, IP, ICMP, UDP, TCP, ARP, DNS, DHCP, FTP,
TFTP, HTTP, POP3, SMTP
Tunneling (VPN)
SSH-VPN client (requires M2M Gateway)
L2TP-VPN client (requires M2M Gateway)
SSH client
Management
WWW, SSH, Telnet and console FTP, TFTP and HTTP
software update
Routing and firewall
Static routing, proxy ARP, port forwarding, IP
masquerading/NAT, firewall
Serial device connectivity
Device server application (IEC 60870-5-104 GW)
Simultaneous GPRS, CSD and SMS
SMS configuration and status reporting
IEC 60870-5-104 and IEC 60870-5-101
IEC 60870-5-104 over TCP or UDP
IEC 60870-5-101 FT 1.2 framing
Local IEC 60870-5-101 polling
ASDU replacer
Packet compressor
Table 6. Physical interfaces
Description
REC601
REC603
Binary
Analog
Binary
Analog
Inputs/Outputs
I
O
I
O
I
O
I
O
Disconnector control
6
3
-
-
16
7
-
-
Battery control
-
2
2
1)
-
-
2
2
1)
-
Motor control
-
1
2)
1
3)
-
-
1
2)
1
3)
-
Transducer input
-
-
1
4)
-
-
-
1
4)
-
Heater control output
-
1
-
-
-
1
-
-
1)
ranges 0...30 V, 0...10 A
2)
Overcurrent
3)
0...15 A
4)
0...5 A
Wireless Controller
1MRS757423 A
REC601/603
Product version: 1.0
16
ABB