Function
Application 1
Application 2
Directional over-power protection GOPPDOP
(32)
Application dependent
Application dependent
Negative sequence based overcurrent
protection DNSPTOC (46)
Application dependent
Application dependent
Two step undervoltage protection UV2PTUV
(27)
Application dependent
Application dependent
Two step overvoltage protection OV2PTOV
(59)
Application dependent
Application dependent
Two step residual overvoltage protection
ROV2PTOV (59N)
Disabled
Enabled
Under frequency protection SAPTUF (81)
(instance 1)
Application dependent
Application dependent
Under frequency protection SAPTUF (81)
(instance 2)
Application dependent
Application dependent
Over frequency protection SAPTOF (81)
(instance 1)
Application dependent
Application dependent
Over frequency protection SAPTOF (81)
(instance 2)
Application dependent
Application dependent
Rate-of-change of frequency protection
SAPFRC (81) (instance 1)
Application dependent
Application dependent
Rate-of-change of frequency protection
SAPFRC (81) (instance 2)
Application dependent
Application dependent
Current circuit supervision CCSRDIF (87)
Enabled
Enabled
Fuse failure supervision SDDRFUF
Enabled
Enabled
Breaker close/trip circuit monitoring
TCSSCBR
Enabled
Enabled
Synchrocheck, energizing check, and
synchronizing SESRSYN (25)
Application dependent
Application dependent
Autorecloser SMBRREC (79)
Enabled
Enabled
2.3.4
Bus coupler in a solidly grounded network
Normally the following fault scenarios require back-up protection functions:
•
Short circuits on one of the busbar sections and short circuits on outgoing lines. For
these faults the four step phase overcurrent protection should be used. The four step
phase overcurrent protection has the possibility of directional function as well as
different time delay characteristics. It is important to base the setting on fault
calculations considering different operational states as well as time delay
coordination with other protections in the system.
•
Phase-to-ground faults one of the busbar sections and phase-to-ground faults on
outgoing lines. For these faults the four step residual overcurrent protection should be
used. The four step residual overcurrent protection has the possibility of directional
1MRK 511 286-UUS A
Section 2
Application
35
Application manual
Summary of Contents for REC650 ANSI
Page 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Page 2: ......
Page 26: ...20...
Page 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Page 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Page 82: ...76...
Page 92: ...86...
Page 170: ...164...
Page 176: ...170...
Page 274: ...268...
Page 288: ...282...
Page 350: ...344...
Page 369: ...363...