A070860 V4 EN
Figure 51:
Clear view
2.
Select the item to be cleared with
or
.
3.
Press
, change the value from
False
to
True
with
or
and press
again. The item is now cleared and the value changes back to
False
.
4.
Repeat steps 2 and 3 to clear other items.
6.4
Changing IED functionality
6.4.1
Creating blockings
PCM600 can be used for creating blockings.
For more information, see PCM600 documentation.
6.4.2
Selecting test mode
The test mode can be activated using the LHMI. The green Ready LED will be
blinking to indicate that the test mode is activated.
1.
Select
Main Menu/Tests/IED test/Test mode
and press
.
A071154 V3 EN
Figure 52:
Entering test mode
2.
Select
Test off
or
Test on
with
or
.
3.
Press
to confirm the selection.
Section 6
1MRS756499 A
Operating procedures
72
RED615
Operation Manual