10.2.6.3
Blocking
M14958-13 v7
It is possible to block overfrequency protection SAPTOF partially or completely,
by binary input signals or by parameter settings, where:
BLOCK:
blocks the START and TRIP outputs
BLKTRIP:
blocks the TRIP output
If the measured voltage level decreases below the setting of
IntBlockLevel
, both the
START and the TRIP outputs are blocked.
10.2.6.4
Design
M14958-24 v9
The frequency measuring element continuously measures the frequency of the
positive sequence voltage and compares it to the setting
StartFrequency
. The
frequency signal is filtered to avoid transients due to switchings and faults in the
power system. The time integrator operates due to a definite delay time. The design
of overfrequency protection SAPTOF is schematically described in figure
.
Frequency
f > StartFrequency
Voltage
start
TRIP
U < IntBlockLevel
block
BLOCK
OR
Definite timer
tReset
tDelay
IEC16000042-1-en.vsdx
trip
START
BLKDMAGN
BLKTRIP
AND
Start
&
Trip
output
logic
IEC16000042 V1 EN-US
Figure 130:
Simplified logic diagram for SAPTOF
Section 10
1MRK 505 394-UEN A
Frequency protection
276
Line differential protection RED650 2.2 IEC
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...