Another alternative is with one three-winding transformer in the protected zone,
shown in Figure
. Observe that in this case, the three-winding power transformer
is seen by the differential protection as two separate power transformers, A and B,
which have one common winding on the HV side.
IEC15000451-2-en.vsdx
IED
IED
A
B
T
T
Prot ected zone
IEC15000451 V2 EN-US
Figure 43:
One three–winding transformer in the protected zone
TraAOnInpCh
M12541-239 v6
This parameter is used to indicate that a power transformer is included in the
protection zone at current terminal X. This can be either a two-winding transformer
Section 6
1MRK 505 393-UEN B
Differential protection
94
Line differential protection RED650 2.2 IEC
Application manual