5
The interval when
IdMinHigh is active is set to 60 s because a power transformer is included in
the protected zone. As both IEDs process the same currents, both must have the same value
set for
IdMinHigh.
6
The unrestrained operate (differential) current limit should greater than the highest through fault
current. This current appears at a three-phase short circuit on the 33 kV side of the transformer
and can be calculated as:
220
2.75
3 (7.0 15.0 24.2)
Through
I
kA
=
=
×
+
+
EQUATION1423 V1 EN-US
(Equation 18)
With a safety margin of 20%:
1.2
1.2 2.75
3.30
5.50
0.6
0.6
Through
I
kA
kA
Idunre
Ibase
kA
kA
×
×
=
=
=
=
EQUATION1424 V1 EN-US
(Equation 19)
7
The cross-block logic should always be active when there is a power transformer in the
protected zone.
Setting example with a small tap transformer in the protected zone
A typical example is shown in Figure
IEC12000193-2-en.vsd
3Id>
3Id>
SA
1700
MVA
SA
1280
MVA
10MVA
ek=10%
138/10kV
3Id>
3Id>
A
B
IEC12000193 V2 EN-US
Figure 46:
Setting example
Input data to calculation:
•
Apparent source power at A side: Ss
A
= 1700 MVA
•
Line impedance from A to tap: Zl
A
= 2.8 Ω
•
Line impedance from tap to B side: Zl
B
= 1.2 Ω
1MRK 505 393-UEN B
Section 6
Differential protection
Line differential protection RED650 2.2 IEC
101
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...