Protection functions in stations B and C operate as slaves (differential function
switched off) so currents are sent to protection function in station A, and received
on channels 2 and 3. To inform the differential algorithm that currents are coming
from the LV sides of the transformers,
TraAOnInpCh
must be set to 2 and
TraBOnInpCh
to 3 (channel1 is reserved for local measurement). This is to ensure
that proper turn ratio and vector group correction is done.
Setting example with a three-winding transformer in the protected
zone
IEC13000296-1-en.vsdx
IED
IED
A
B
T
T
IEC13000296 V2 EN-US
Figure 50:
Three-winding transformer in the zone
Settings
Station A
Station B
PDIF
L3TCPDIF
L3TCPDIF
NoOfUsedCTs
3
3
T
raAOnInpCh
2
1
TraBOnInpCh
3
2
Currents from the secondary and tertiary windings of the power transformer are
connected to one line differential protection IED. Currents for each CT group are
sent to the IED at station A by the LDCM. To inform the differential algorithm that
currents are coming from the LV sides of the transformers,
TraAOnInpCh
must be
set to 2 and
TraBOnInpCh
to 3 (channel1 is reserved for local measurement). This
is to ensure that proper turn ratio and vector group correction is done.
1MRK 505 393-UEN B
Section 6
Differential protection
Line differential protection RED650 2.2 IEC
105
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...