accidental event be given precaution, the phase-to-earth reach (RFPEZx) of all
instantaneous zones has to be set below the emergency load for the pole-open
situation. Again, this is only for the application where there is a risk that one
breaker pole would open without a preceding fault. If this never happens, for
example when there is no parallel circuit, there is no need to change any phase-to-
earth reach according to the pole-open scenario.
7.1.3.9
Other settings
GUID-9D65B411-6FE2-433B-AE6C-C6DD716D1181 v7
IMinOpPEZx
and
IMinOpPPZx
The ability for a specific loop and zone to issue a start or a trip is inhibited if the
magnitude of the input current for this loop falls below the threshold value defined
by these settings. The output of a phase-to-earth loop Ln is blocked if ILn <
IminOpPE
(Zx). In is the RMS value of the fundamental current in phase n.
The output of a phase-to-phase loop LmLn is blocked if ILmLn <
IMinOpPP
(Zx).
ILmLn is the RMS value of the vector difference between phase currents Lm and
Ln.
Both current limits
IMinOpPEZx
and
IMinOpPPZx
are automatically reduced to
75% of regular set values if the zone is set to operate in reverse direction, that is,
OperationDir
is set to
Reverse
.
OpModePPZx
and
OpModePEZx
These settings, two per zone (x=1,2..5&RV), with options {Off, Quadrilateral,
Mho, Offset}, are used to set the operation and characteristic for phase-to-earth and
phase-to-phase faults, respectively.
For example, in one zone it is possible to choose Mho characteristic for the three
Ph-Ph measuring loops and Quadrilateral characteristic for the three Ph-E
measuring loops.
DirModeZx
This setting defines the operating direction for zones Z3, Z4 and Z5 (the
directionality of zones Z1, Z2 and ZRV is fixed). The options are
Non-directional
,
Forward
or
Reverse
. The result from respective set value is illustrated in figure
where the positive impedance corresponds to the direction out on the protected
line.
Section 7
1MRK 505 393-UEN B
Impedance protection
130
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...