IEC05000182-2-en.vsdx
R
X
R
X
R
X
Non-directional
Forward
Reverse
IEC05000182 V2 EN-US
Figure 64:
Directional operating modes of the distance measuring zones 3 to
5
tPPZx
,
tPEZx
,
TimerModeZx
,
ZoneLinkStart
and
TimerLinksZx
The logic for the linking of the timer settings can be described with a module
diagram. The figure
shows only the case when
TimerModeZx
is selected to
Ph-
Ph
and
Ph-E
.
1MRK 505 393-UEN B
Section 7
Impedance protection
Line differential protection RED650 2.2 IEC
131
Application manual