Common base IED values for the primary current (
IBase
), primary voltage (
UBase
)
and primary power (
SBase
) are set in global base values for settings function
GBASVAL.
GlobalBaseSel
: Selects the global base value group used by the function to define
IBase
,
UBase
and
SBase
as applicable.
MeasType
: Selection of discrete Fourier filtered (
DFT
) or true RMS filtered (
RMS
)
signals.
RMS
is used when the harmonic contents are to be considered, for example
in applications with shunt capacitors.
Operation
: The protection can be set to
On
or
Off
.
AngleRCA
: Protection characteristic angle set in degrees. If the angle of the fault
loop current has the angle RCA, the direction to the fault is forward.
AngleROA
: Angle value, given in degrees, to define the angle sector of the
directional function, shown in Figure
StartPhSel
: Number of phases, with high current, required for operation. The
setting possibilities are:
1 out of 3
,
2 out of 3
and
3 out of 3
. The default setting is
1
out of 3
.
IMinOpPhSel
: Minimum current setting level for releasing the directional start
signals in % of
IB
. This setting should be less than the lowest step setting. The
default setting is 7% of
IB
.
2ndHarmStab
: Operate level of 2nd harmonic current restrain set in % of the
fundamental current. The setting range is
5 - 100
% in steps of 1%. The default
setting is 20%.
Section 8
1MRK 505 393-UEN B
Current protection
154
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...