txMin
: Minimum operate time for all inverse time characteristics. At high currents
the inverse time characteristic might give a very short operation time. By setting
this parameter the operation time of the step can never be shorter than the setting.
Setting range: 0.000 - 60.000s in steps of 0.001s.
IxMult
: Multiplier for scaling of the current setting value. If a binary input signal
ENMULTx (enableMultiplier) is activated the current operation level is increased
by this setting constant. Setting range: 1.0-10.0
IMinx
Operate time
Current
tx
txMin
IEC10000058
IEC10000058 V2 EN-US
Figure 74:
Minimum operate current and operate time for inverse time
characteristics
In order to fully comply with the definition of the curve, the setting parameter
txMin
shall be set to a value equal to the operating time of the selected inverse
curve for twenty times the set current pickup value. Note that the operate time is
dependent on the selected time multiplier setting
kx
.
ResetTypeCrvx
: The reset of the delay timer can be made as shown in Table
.
Table 16:
Reset possibilities
Curve name
Curve index no.
Instantaneous
1
IEC Reset (constant time)
2
ANSI Reset (inverse time)
3
The delay characteristics are described in
Technical manual
. There are some
restrictions regarding the choice of the reset delay.
For the definite time delay characteristics, the possible delay time setting
instantaneous (1) and IEC (2 = set constant time reset).
1MRK 505 393-UEN B
Section 8
Current protection
Line differential protection RED650 2.2 IEC
157
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...