where it is considered that:
the operate time of overcurrent protection B1 is 40 ms
the breaker open time
is 100 ms
the resetting time of protection A1
is 40 ms and
the additional margin
is 40 ms
8.3
Instantaneous residual overcurrent protection
EFPIOC
IP14508-1 v3
8.3.1
Identification
M14887-1 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Instantaneous residual overcurrent
protection
EFPIOC
IN>>
IEF V1 EN-US
50N
8.3.2
Application
M12699-3 v5
In many applications, when fault current is limited to a defined value by the object
impedance, an instantaneous earth-fault protection can provide fast and selective
tripping.
The Instantaneous residual overcurrent EFPIOC, which can operate in 15 ms (50
Hz nominal system frequency) for faults characterized by very high currents, is
included in the IED.
8.3.3
Setting guidelines
IP14985-1 v1
M12762-44 v2
M12762-4 v4
The parameters for the Instantaneous residual overcurrent protection EFPIOC are
set via the local HMI or PCM600.
Some guidelines for the choice of setting parameter for EFPIOC is given.
M12762-6 v8
Common base IED values for primary current (
IBase
), primary voltage (
UBase
)
and primary power (
SBase
) are set in the global base values for settings function
GBASVAL.
1MRK 505 393-UEN B
Section 8
Current protection
Line differential protection RED650 2.2 IEC
163
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...