100
2
2
3
IBase
I
I
EQUATION1520 V5 EN-US
(Equation 126)
where:
I2
is the maximal negative sequence current during normal operating conditions, plus a margin
of 10...20%
IBase
is the base current for the function according to the setting
GlobalBaseSel
11.2.3.4
Zero sequence based
M13683-43 v8
The IED setting value
3U0>
is given in percentage of the base voltage
UBase
. The
setting of
3U0>
should not be set lower than the value that is calculated according
.
100
3
0
3
0
3
UBase
U
U
EQUATION1521 V4 EN-US
(Equation 127)
where:
3U0
is the maximal zero sequence voltage during normal operation conditions, plus a margin of
10...20%
UBase is the base voltage for the function according to the setting
GlobalBaseSel
The setting of the current limit
3I0<
is done in percentage of
IBase
. The setting of
3I0<
must be higher than the normal unbalance current that might exist in the
system. The setting can be calculated according to equation
3 0
3 0
100
I
I
IBase
=
×
<
EQUATION2293 V3 EN-US
(Equation 128)
where:
3I0<
is the maximal zero sequence current during normal operating conditions, plus a margin of
10...20%
IBase
is the base current for the function according to the setting
GlobalBaseSel
11.2.3.5
Delta U and delta I
GUID-02336F26-98C0-419D-8759-45F5F12580DE v7
Set the operation mode selector
OpDUDI
to
On
if the delta function shall be in
operation.
1MRK 505 393-UEN B
Section 11
Secondary system supervision
Line differential protection RED650 2.2 IEC
213
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...