via the extinguishing capacitors in the circuit breakers. This voltage
can be as high as 30% or more of the base line voltage.
Because the setting ranges of the threshold voltages
UHighBusEnerg
/
UHighLineEnerg
and
ULowBusEnerg
/
ULowLineEnerg
partly overlap each other,
the setting conditions may be such that the setting of the non-energized threshold
value is higher than that of the energized threshold value. The parameters must
therefore be set carefully to avoid overlapping.
UMaxEnerg
This setting is used to block the closing when the voltage on the live side is above
the set value of
UMaxEnerg
.
tAutoEnerg
and
tManEnerg
The purpose of the timer delay settings,
tAutoEnerg
and
tManEnerg
, is to ensure
that the dead side remains de-energized and that the condition is not due to a
temporary interference. Should the conditions not persist for the specified time, the
delay timer is reset and the procedure is restarted when the conditions are fulfilled
again. Circuit breaker closing is thus not permitted until the energizing condition
has remained constant throughout the set delay setting time.
12.2
Autorecloser for 1 phase, 2 phase and/or 3 phase
operation SMBRREC
IP14559-1 v6
12.2.1
Identification
M14890-1 v7
Function Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Autorecloser for 1 phase, 2 phase and/or 3
phase
SMBRREC
5(0 -->1)
IEC15000204 V1 EN-US
79
12.2.2
Application
M12391-3 v8
Automatic reclosing is a well-established method for the restoration of service in a
power system after a transient line fault. The majority of line faults are flashovers,
which are transient by nature. When the power line is switched off by the operation
of line protection and line breakers, the arc de-ionizes and recovers its ability to
withstand voltage at a somewhat variable rate. Thus, a certain dead time with a de-
energized line is necessary. Line service can then be resumed by automatic
1MRK 505 393-UEN B
Section 12
Control
Line differential protection RED650 2.2 IEC
229
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...