created internally with the manual closing going through the synchrocheck
function. An example of lock-out logic.
Lock-out
RXMD1
11
12
21
MAIN ZAK CLOSE
CLOSE COMMAND
SMBO
OR
SMBRREC
OR
CCRBRF
BU-TRIP
ZCVPSOF-TRIP
INHIBIT
UNSUCCL
TRBU
IEC05000315-4-en.vsd
IEC05000315-WMF V4 EN-US
Figure 103:
Lock-out arranged with an external lock-out relay
CLOSE COMMAND
OR
SMBRREC
OR
CCRBRF
BU-TRIP
ZCVPSOF-TRIP
INHIBI T
UNSUCCL
TRBU
SMPPTRC
AND
RESET LOCK-OUT
OR
OR
SESRSYN
Functional key,
SOFTWARE
OR IO RESET
MANSYOK
MAN CLOSE
SMBRREC CLO SE
CLLKOUT
RSTLKOUT
SETLKO UT
IEC05 000 316-4-en.vsdx
SMBO
MANENOK
IEC05000316-WMF V4 EN-US
Figure 104:
Lock-out arranged with internal logic with manual closing going
through in IED
12.2.2.20
Evolving fault
M12391-217 v4
An evolving fault starts as a single-phase fault which leads to single-phase tripping
and then the fault spreads to another phase. The second fault is then cleared by
three-phase tripping.
The auto recloser will first receive a start signal (
START
) without any three-phase
signal (
TR3P
). The auto recloser will start a single-phase auto reclosing sequence,
if programmed to do so. At the evolving fault clearance there will be a new
START
signal and three-phase trip information,
TR3P
. The single-phase auto reclosing
sequence will then be stopped, and instead the timer,
t1 3Ph
, for three-phase auto
Section 12
1MRK 505 393-UEN B
Control
240
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...