reclosing will be started from zero. The sequence will continue as a three-phase
auto reclosing sequence, if it is a selected alternative reclosing mode. The second
fault which can be single-phase is tripped three-phase because the trip function
(SMPPTRC) in the IED has an evolving fault timer which ensures that the second
fault is always tripped three-phase. For other types of relays where the relays do
not include this function, the
PREP3PH
output (or the inverted
PERMIT1PH
output) is used to prepare the other sub-system for three-phase tripping. This signal
will, for evolving fault situations, be activated a short time after the first trip has
reset and will thus ensure that new starts (trips) will be three phase.
12.2.2.21
Automatic continuation of the auto reclosing sequence
M12391-223 v5
The auto recloser can be programmed to proceed to the next auto reclosing shots (if
multiple shots are selected) even if start signals are not received from protection
functions, but the circuit breaker is still not closed. This is done by setting
AutoCont
=
On
and
tAutoContWait
to the required delay for the function to proceed
without a new start.
12.2.2.22
Thermal overload protection holding the auto recloser back
M12391-226 v3
If the
THOLHOLD
input (thermal overload protection holding auto reclosing back)
is activated, it will keep the auto recloser on a hold until it is reset. There may thus
be a considerable delay between start of the auto recloser and the breaker closing
command to the circuit breaker. An external logic limiting the time and sending an
inhibit to the
INHIBIT
input can be used. The input can also be used to set the auto
recloser on hold for a longer or shorter period.
12.2.3
Setting guidelines
IP14929-1 v1
12.2.3.1
Configuration
M12399-3 v3
Use the PCM600 configuration tool to configure signals.
Auto recloser function parameters are set via the local HMI or Parameter Setting
Tool (PST). Parameter Setting Tool is a part of PCM600.
Recommendations for input signals
M12399-7 v10
and default factory configuration for examples.
BLKOFF
Used to unblock the auto recloser when it has been blocked due to activating
BLKON
input or by an unsuccessful auto reclosing attempt if the
BlockByUnsucCl
setting is set to
On
.
BLKON
Used to block the auto recloser, for example, when certain special service
conditions arise. When used, blocking must be reset with
BLKOFF
.
1MRK 505 393-UEN B
Section 12
Control
Line differential protection RED650 2.2 IEC
241
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...