RSTCOUNT
There is a counter for each type of auto reclosing and one for the total number of
circuit breaker close commands issued. All counters are reset with the
RSTCOUNT
input or by an IEC 61850 command.
SKIPHS
The high-speed auto reclosing sequence can be skipped and be replaced by normal
auto reclosing sequence by activating
SKIPHS
input before the
STARTHS
high-
speed start input is activated. The replacement is done for the 1st shot.
START
The
START
input should be connected to the trip function (SMPPTRC) output,
which starts the auto recloser for 1/2/3-phase operation. It can also be connected to
a binary input for start from an external contact. A logical OR-gate can be used to
combine the number of start sources.
If
StartByCBOpen
is used, the circuit breaker open condition shall
also be connected to the
START
input.
STARTHS, Start high-speed auto reclosing
It may be used when one wants to use two different dead times in different
protection trip operations. This input starts the dead time
t1 3PhHS
. High-speed
reclosing shot 1 started by this input is without a synchronization check.
SYNC
This input is connected to the internal synchrocheck function when required or to
an external device for synchronism. If neither internal nor external synchronism or
energizing check is required, it can be connected to a permanently high source,
TRUE. The signal is required for three-phase shots 1-5 to proceed (Note! Not the
high-speed step).
THOLHOLD
Signal “Thermal overload protection holding back auto reclosing”. It can be
connected to a thermal overload protection trip signal which resets only when the
thermal content has fallen to an acceptable level, for example, 70%. As long as the
signal is high, indicating that the line is hot, the auto reclosing is held back. When
the signal resets, a reclosing cycle will continue. Observe that this have a
considerable delay. Input can also be used for other purposes if for some reason the
auto reclosing shot needs to be halted.
TR2P and TR3P
Signals for two-phase and three-phase trip. They are usually connected to the
corresponding output of the trip function block. They control the choice of dead
time and the auto reclosing cycle according to the selected program. Signal TR2P
1MRK 505 393-UEN B
Section 12
Control
Line differential protection RED650 2.2 IEC
243
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...