12.3.7.1
Bay control (QCBAY)
M16670-3 v7
If the parameter
AllPSTOValid
is set to
No priority
, all originators from local and
remote are accepted without any priority.
If the parameter
RemoteIncStation
is set to
Yes
, commands from IEC 61850-8-1
clients at both station and remote level are accepted, when the QCBAY function is
in Remote. If set to
No
, the command LocSta controls which operator place is
accepted when QCBAY is in Remote. If LocSta is true, only commands from
station level are accepted, otherwise only commands from remote level are
accepted.
The parameter
RemoteIncStation
has only effect on the IEC
61850-8-1 communication. Further, when using IEC 61850 edition
1 communication, the parameter should be set to
Yes
, since the
command LocSta is not defined in IEC 61850-8-1 edition 1.
12.3.7.2
Switch controller (SCSWI)
M16673-3 v6
The parameter
CtlModel
specifies the type of control model according to IEC
61850. The default for control of circuit breakers, disconnectors and earthing
switches the control model is set to
SBO Enh
(Select-Before-Operate) with
enhanced security.
When the operation shall be performed in one step, and no monitoring of the result
of the command is desired, the model direct control with normal security is used.
At control with enhanced security there is an additional supervision of the status
value by the control object, which means that each command sequence must be
terminated by a termination command.
The parameter
PosDependent
gives permission to operate depending on the
position indication, that is, at
Always permitted
it is always permitted to operate
independent of the value of the position. At
Not perm at 00/11
it is not permitted to
operate if the position is in bad or intermediate state.
tSelect
is the maximum allowed time between the select and the execute command
signal, that is, the time the operator has to perform the command execution after
the selection of the object to operate. When the time has expired, the selected
output signal is set to false and a cause-code is given.
The time parameter
tResResponse
is the allowed time from reservation request to
the feedback reservation granted from all bays involved in the reservation function.
When the time has expired, the control function is reset, and a cause-code is given.
tSynchrocheck
is the allowed time for the synchrocheck function to fulfill the close
conditions. When the time has expired, the function tries to start the synchronizing
1MRK 505 393-UEN B
Section 12
Control
Line differential protection RED650 2.2 IEC
265
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...