provides to the system operator fast and easy overview of the present status of the
power system. Additionally, it can be used during testing and commissioning of
protection and control IEDs in order to verify proper operation and connection of
instrument transformers (CTs and VTs). During normal service by periodic
comparison of the measured value from the IED with other independent meters the
proper operation of the IED analog measurement chain can be verified. Finally, it
can be used to verify proper direction orientation for distance or directional
overcurrent protection function.
The available measured values from an IED are depending on the
actual hardware (TRM) and the logic configuration made in
PCM600.
All measured values can be supervised with four settable limits that is, low-low
limit, low limit, high limit and high-high limit. A zero clamping reduction is also
supported, that is, the measured value below a settable limit is forced to zero which
reduces the impact of noise in the inputs.
Dead-band supervision can be used to report measured signal value to station level
when change in measured value is above set threshold limit or time integral of all
changes since the last time value updating exceeds the threshold limit. Measure
value can also be based on periodic reporting.
Main menu/Measurement/Monitoring/Service values/CVMMXN
The measurement function, CVMMXN, provides the following power system
quantities:
•
P, Q and S: three phase active, reactive and apparent power
•
PF: power factor
•
U: phase-to-phase voltage amplitude
•
I: phase current amplitude
•
F: power system frequency
,
The measuring functions CMMXU, VMMXU and VNMMXU provide physical
quantities:
•
I: phase currents (amplitude and angle) (CMMXU)
•
U: voltages (phase-to-earth and phase-to-phase voltage, amplitude and angle)
(VMMXU, VNMMXU)
The CVMMXN function calculates three-phase power quantities by using
fundamental frequency phasors (DFT values) of the measured current and voltage
signals. The measured power quantities are available either, as instantaneously
calculated quantities or, averaged values over a period of time (low pass filtered)
depending on the selected settings.
Section 15
1MRK 505 393-UEN B
Monitoring
318
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...