Trip value rec
Fault locator
Event list
Event recorder
Indications
Disturbance
recorder
Disturbance Report
Binary signals
Analog signals
DRPRDRE
FL
IEC09000336-3-en.vsdx
AxRADR
BxRBDR
IEC09000336 V3 EN-US
Figure 138:
Disturbance report functions and related function blocks
For Disturbance report function there are a number of settings which also
influences the sub-functions.
Three LED indications placed above the LCD screen makes it possible to get quick
status information about the IED.
Green LED:
Steady light
In Service
Flashing light
Internal failure
Dark
No power supply
Yellow LED:
Steady light
Triggered on binary signal N with SetLEDx = Start (or Start and
Trip)
Flashing light
The IED is in test mode
Red LED:
Steady light
Triggered on binary signal N with SetLEDx = Trip (or Start and
Trip)
Flashing
The IED is in configuration mode
Section 15
1MRK 505 393-UEN B
Monitoring
338
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...