18.6.2.1
Settings for RS485 and optical serial communication
M17109-118 v12
General settings
SPA, DNP and IEC 60870-5-103 can be configured to operate on the SLM optical
serial port while DNP and IEC 60870-5-103 additionally can utilize the RS485
port. A single protocol can be active on a given physical port at any time.
Two different areas in the HMI are used to configure the IEC 60870-5-103
protocol.
1. The port specific IEC 60870-5-103 protocol parameters are configured under:
Main menu/Configuration/Communication/Station Communication/
IEC60870-5-103/
•
<config-selector>
•
SlaveAddress
•
BaudRate
•
RevPolarity (optical channel only)
•
CycMeasRepTime
•
MasterTimeDomain
•
TimeSyncMode
•
EvalTimeAccuracy
•
EventRepMode
•
CmdMode
•
RepIntermediatePos
<config-selector> is:
•
“OPTICAL103:1” for the optical serial channel on the SLM
•
“RS485103:1” for the RS485 port
2. The protocol to activate on a physical port is selected under:
Main menu/Configuration/Communication/Station Communication/Port
configuration/
•
RS485 port
•
RS485PROT:1 (off, DNP, IEC103)
•
SLM optical serial port
•
PROTOCOL:1 (off, DNP, IEC103, SPA)
Section 18
1MRK 505 393-UEN B
Station communication
388
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...