IEC07000199 V3 EN-US
Figure 171:
Configuration for using an instance in task time group 2 as DFT
reference.
Assume instance SMAI4:16 in task time group 2 has been selected in the
configuration to control the frequency tracking for all instances. Observe that the
selected reference instance (i.e. frequency tracking master) must be a voltage type.
Observe that positive sequence voltage is used for the frequency tracking feature.
For task time group 1 this gives the following settings (see Figure
numbering):
SMAI1:1 – SMAI12:12:
DFTReference
=
ExternalDFTRef
to use DFTSPFC input
as reference (SMAI4:16)
For task time group 2 this gives the following settings:
SMAI1:13:
DFTRefExtOut
=
DFTRefGrp4
to route SMAI4:16 reference to the
SPFCOUT output,
DFTReference
=
DFTRefGrp4
for SMAI1:13 to use SMAI4:16
) SMAI2:14 – SMAI12:24:
DFTReference
=
DFTRefGrp4
to use SMAI4:16 as reference.
For task time group 3 this gives the following settings:
SMAI1:25 – SMAI12:36:
DFTReference
=
ExternalDFTRef
to use DFTSPFC
input as reference (SMAI4:16)
Section 21
1MRK 505 393-UEN B
Basic IED functions
414
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...