The parameter
Mod
of any specific function block can be configured under
Main
menu/Test/Function test modes/Communication/Station Communication
The parameter Mod can be set on the LHMI to the same values as for the
DataObject Mod of the Root LD.LNN0 to
On
,
Off
,
TestBlocked
,
Test
or
Blocked
.
For Example, Main menu/ Test/ Function test modes/ Differential protection/
GeneratorDiff(87G,3Id/I>)/ GENPDIF(87G,3Id/I>):1.
It is possible that the behavior of the function block TESTMODE is also influenced
by other sources as well, independent of the mode communicated via the
IEC61850-8-1 station bus. For example the insertion of the test handle into the test
switch with its auxiliary contact is connected to a BI on the IED and further inside
the configuration to the input IED_TEST on the function block TESTMODE.
Another example is when loss of Service Values appears, or as explained above the
setting via the LHMI.
When setting via PST or LHMI the parameter
Operation
of any function in an IED
is set to
Off
, the function is not executed and the behavior (beh) is set to
Off
and it is
not possible to override it. When a behavior of a function is
Off
the function will
not execute. The related
Mod
keeps its current state.
When IEC 61850 Mod of a function is set to
Off
or
Blocked
, the
Start LED on the LHMI will be set to flashing to indicate the
abnormal operation of the IED.
The IEC 61850-7-4 gives a detailed overview over all aspects of the test mode and
other states of mode and behavior. The status of a function block behavior
Beh
is
shown on the LHMI under the
Main menu/Test/Function status/Function group/
Function block descriptive name/LN name/Outputs
.
•
When the
Beh
of a function block is set to
Test
, the function block is not
blocked and all control commands with a test bit are accepted.
•
When the
Beh
of a function block is set to
Test/blocked
, all control commands
with a test bit are accepted. Outputs to the process via a non-IEC 61850 link
data are blocked by the function block. Only process-related outputs on
function blocks related to primary equipment are blocked. If there is an XCBR
function block used, the outputs
EXC_Open
and
EXC_Close
are blocked.
•
When the
Beh
of a function block is set to
Blocked
, all control commands with
a test bit are accepted. Outputs to the process via a non-IEC 61850 link data
are blocked by the function block. In addition, the function block can be
blocked when their
Beh
is
blocked
. This can be done if the function block has
a block input.
The block status of a component is shown on the LHMI as the
Blk
output under the
same path as for
Beh:Main menu/Test/Function status/Function group/Function
block descriptive name/LN name/Outputs
. If the
Blk
output is not shown, the
component cannot be blocked.
Section 21
1MRK 505 393-UEN B
Basic IED functions
416
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...