4.2.2.4
Examples on how to connect, configure and set CT inputs for most
commonly used CT connections
SEMOD55055-296 v7
Figure
defines the marking of current transformer terminals commonly used
around the world:
In the SMAI function block, you have to set if the SMAI block is
measuring current or voltage. This is done with the parameter:
AnalogInputType
: Current/Voltage. The
ConnectionType
: phase -
phase/phase-earth and
GlobalBaseSel
.
I
Sec
I
P
ri
S1 (X1)
P1
(H1)
P2
(H2)
S2 (X2)
P2
(H2)
P1
(H1)
x
x
a)
b)
c)
en06000641.vsd
S2 (X2)
S1 (X1)
IEC06000641 V1 EN-US
Figure 9:
Commonly used markings of CT terminals
Where:
a)
is symbol and terminal marking used in this document. Terminals marked with a square
indicates the primary and secondary winding terminals with the same (that is, positive)
polarity
b) and
c)
are equivalent symbols and terminal marking used by IEC (ANSI) standard for CTs. Note that
for these two cases the CT polarity marking is correct!
It shall be noted that depending on national standard and utility practices, the rated
secondary current of a CT has typically one of the following values:
•
1A
•
5A
However, in some cases, the following rated secondary currents are used as well:
•
2A
•
10A
The IED fully supports all of these rated secondary values.
1MRK 505 393-UEN B
Section 4
Analog inputs
Line differential protection RED650 2.2 IEC
45
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...