CT signal disappears when all currents are again normal, or when all three currents
become zero.
•
Setting parameter
OpenCTEnable
enables and disables this feature.
•
Setting parameter
OCTBlockEn
enables and disables the blocking of
differential function once an open CT is detected. When
OCTBlockEn
is set to
OFF, only an alarm signal is issued.
•
Setting parameter
tOCTAlarmDelay
defines the time delay after which the
alarm signal is given.
•
Setting parameter
tOCTResetDelay
defines the time delay after which the open
CT condition resets once the defective CT circuits have been repaired.
•
Once the open CT condition has been detected, all the differential protection
functions are blocked except the unrestrained (instantaneous) differential
protection. However, there is no guarantee that an unwanted disconnection of
the protected circuit can always be prevented.
•
For applications where the currents from two CTs are summated and sent over
LDCM, the output
OPENCT
must be connected to CTFAIL on LDLPSCH
logic in order for the Open CT detection to operate properly. Observe that
summation of currents shall be avoided where possible.
The outputs of the open CT conditions are
OPENCT
and
OPENCTAL
.
•
OPENCT
: Open CT detected
•
OPENCTAL
: Alarm issued after the setting delay
Outputs (positive integer) for information on the local HMI:
•
OPENCTIN
: Open CT in CT group inputs (1 for input 1 and 2 for input 2)
•
OPENCTPH
: Open CT with phase information (1 for phase L1, 2 for phase L2,
3 for phase L3)
6.1.3
Setting guidelines
SEMOD54832-1 v3
M12541-86 v4
Line differential protection receives information about currents from all line
terminals and evaluates this information in three different analysis blocks. The
results of these analyses are then forwarded to an output logic, where the
conditions for trip or no trip are checked.
The three current analyses are:
•
Percentage restrained differential analysis
•
The 2
nd
and 5
th
harmonic analysis (only if there is a power transformer
included in the protected circuit)
•
Internal/external fault discriminator
6.1.3.1
General settings
M12541-93 v3
Section 6
1MRK 505 393-UEN B
Differential protection
86
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...