0
1
0
1
0
1
0
Im( )
(2
3
)
(2
)
A
X
R
R
R
R
X
X
=
× × +
+ ×
+
× ×
+
EQUATION1286 V1 EN-US
(Equation 48)
The real component of the KU factor is equal to equation
.
Re
Re
Re
Im
K
A
X
A
A
u
m
( )
= +
( )
⋅
( )
+
( )
1
0
2
2
2
EQUATION1287 V3 EN-US
(Equation 49)
The imaginary component of the same factor is equal to equation
( )
( )
( )
( )
2
0
2
2
Im
Im
Re
Im
m
U
A X
K
A
A
×
=
+
é
ù
é
ù
ë
û
ë
û
EQUATION1288 V2 EN-US
(Equation 50)
Ensure that the underreaching zones from both line ends will overlap a sufficient
amount (at least 10%) in the middle of the protected circuit.
7.1.2.7
Tapped line application
GUID-740E8C46-45EE-4CE8-8718-9FAE658E9FCE v1
GUID-7AA566A4-B6E9-41A7-9927-4DAB50BE8D1A v1
C
B
BC
IEC09000160-3-en.vsd
A
IEC09000160 V3 EN-US
Figure 61:
Example of tapped line with Auto transformer
Section 7
1MRK 505 393-UEN B
Impedance protection
120
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...