IN
>
One phase-to-earth
fault
3I
0
IN
>
3I
01
IEC05000155-en-2.vsd
IEC05000155 V3 EN-US
Figure 89:
Step 2, selectivity calculation
A second criterion for step 2 is according to equation
.
1
1
0
step2
step1
0
3I
I
.2
I
3I
³
×
×
EQUATION1203 V4 EN-US
(Equation 117)
where:
I
step1
is the current setting for step 1 on the faulted line.
Step 3
M15282-164 v6
This step has directional function and a time delay slightly larger than step 2, often
0.8 s. Step 3 shall enable selective trip of earth faults having higher fault resistance
to earth, compared to step 2. The requirement on step 3 is selectivity to other earth-
fault protections in the network. One criterion for setting is shown in Figure
IEC05000156-3-en.vsd
IN
>
One phase-to-
earth fault
3I
0
IN
>
3I
02
IEC05000156 V3 EN-US
Figure 90:
Step 3, Selectivity calculation
1
0
step3
step2
02
3I
I
.2
I
3I
³
×
×
EQUATION1204 V4 EN-US
(Equation 118)
where:
I
step2
is the chosen current setting for step 2 on the faulted line.
1MRK 505 393-UEN B
Section 8
Current protection
Line differential protection RED650 2.2 IEC
179
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...