Example for use of GRP_OFF signal in FXDSIGN
The Restricted earth fault function (REFPDIF) can be used both for auto-
transformers and normal transformers.
When used for auto-transformers, information from both windings parts, together
with the neutral point current, needs to be available to the function. This means that
three inputs are needed.
I3PW1CT1
I3PW2CT1
I3P
REFPDIF
IEC09000619_3_en.vsd
IEC09000619 V3 EN-US
Figure 132:
REFPDIF function inputs for autotransformer application
For normal transformers only one winding and the neutral point is available. This
means that only two inputs are used. Since all group connections are mandatory to
be connected, the third input needs to be connected to something, which is the
GRP_OFF signal in FXDSIGN function block.
I3PW1CT1
I3PW2CT1
I3P
REFPDIF
GRP_OFF
FXDSIGN
IEC09000620_3_en.vsd
IEC09000620 V3 EN-US
Figure 133:
REFPDIF function inputs for normal transformer application
14.8
Boolean 16 to Integer conversion B16I
SEMOD175715-1 v1
14.8.1
Identification
SEMOD175721-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Boolean 16 to integer conversion
B16I
-
-
Section 14
1MRK 505 393-UEN B
Logic
306
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...