14.13.2
Application
GUID-4C6D730D-BB1C-45F1-A719-1267234BF1B9 v1
The function gives the possibility to monitor the level of integer values in the
system relative to each other or to a fixed value. It is a basic arithmetic function
that can be used for monitoring, supervision, interlocking and other logics.
14.13.3
Setting guidelines
GUID-ADA3E806-BEF1-4D15-B270-207386A0AEE4 v2
For proper operation of comparison the set value should be set within the range of
± 2 ×10
9
.
Setting procedure on the IED:
EnaAbs
: This setting is used to select the comparison type between signed and
absolute values.
•
Absolute
: Comparison is performed on absolute values of input and reference
values
•
Signed
: Comparison is performed on signed values of input and reference
values.
RefSource
: This setting is used to select the reference source between input and
setting for comparison.
•
Input REF
: The function will take reference value from input REF
•
Set Value
: The function will take reference value from setting
SetValue
SetValue
: This setting is used to set the reference value for comparison when
setting
RefSource
is selected as
SetValue
.
14.13.4
Setting example
GUID-13302FD6-1585-42FE-BD6D-44F231982C59 v2
For absolute comparison between inputs:
Set the
EnaAbs
=
Absolute
Set the
RefSource
=
Input REF
Similarly for Signed comparison between inputs
Set the
EnaAbs
=
Signed
Set the
RefSource
=
Input REF
For absolute comparison between input and setting
Set the
EnaAbs
=
Absolute
1MRK 505 393-UEN B
Section 14
Logic
Line differential protection RED650 2.2 IEC
313
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...