Table 30:
General settings parameters for the Measurement function
Setting
Short description
Selected
value
Comment
Operation
Operation
Off/On
On
Function must be
On
PowAmpFact
Amplitude factor to scale power
calculations
1.000
Typically no scaling is required
PowAngComp
Angle compensation for phase
shift between measured I & U
180.0
Typically no angle compensation
is required. However here the
required direction of P & Q
measurement is towards busbar
(Not per IED internal default
direction). Therefore angle
compensation have to be used in
order to get measurements in
aliment with the required
direction.
Mode
Selection of measured current
and voltage
L1L2
Only UL1L2 phase-to-phase
voltage is available
k
Low pass filter coefficient for
power measurement, U and I
0.00
Typically no additional filtering is
required
UGenZeroDb
Zero point clamping in % of
Ubase
25
Set minimum voltage level to
25%
IGenZeroDb
Zero point clamping in % of
Ibase
3
Set minimum current level to 3%
UBase (set in
Global base)
Base setting for voltage level in
kV
35.00
Set LV side rated phase-to-
phase voltage
IBase (set in
Global base)
Base setting for current level in
A
495
Set transformer LV winding rated
current
SBase (set in
Global base)
Base setting for power in MVA
31.5
Set based on rated power
15.2
Gas medium supervision SSIMG
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3
15.2.1
Identification
GUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Insulation gas monitoring function
SSIMG
-
63
15.2.2
Application
GUID-A840E38C-CC42-4995-A569-A6092DDB81B2 v5
Gas medium supervision (SSIMG) is used for monitoring the circuit breaker
condition. Proper arc extinction by the compressed gas in the circuit breaker is very
important. When the pressure becomes too low compared to the required value, the
circuit breaker operation shall be blocked to minimize the risk of internal failure.
Binary information based on the gas pressure in the circuit breaker is used as an
1MRK 505 393-UEN B
Section 15
Monitoring
Line differential protection RED650 2.2 IEC
327
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...